AEG Protect PV.500-MH PV.500-MH Manuel D’Utilisation

Page de 68
Protect PV.500-MH Operating Instructions 
40 of 68 
80000043212 BAL 
 
Unit Monitoring Systems 
 
Fault/Message 
Deac-
tivat-ing
 
Self-
acknow-led
ging 
Signalling 
DOU message 
Monitoring 
fan fault cabinet fan 
 
 
!Fan failure! 
Monitoring 
fan fault stack fans 
  X 
!Fan 
failure! 
Monitoring K91 
feedback signal fan contactor 
 
 
K91: !Switch feedback fault! 
Monitoring K7 
feedback signal INV 
output contactor
 
 
 
#Fault K7 feedback signal# 
Monitoring 
parameter limits 
 
 
!Parameter limit fault! 
Monitoring 
PCB ID 
X    
#Self-test 
fault# 
Monitoring 
EEPROM 
 
 
#EEPROM fault# 
Monitoring 
serial EEPROM 
  X 
!System 
fault! 
Monitoring 
Watchdog 
 
 
#Watchdog# 
Monitoring 
15 V supply voltage 
 
 
#15 V supply voltage fault# 
Monitoring 
IGBT stack 
 
 
#Stack fault# 
Monitoring 
short-circuit/overload 
X    
#Short 
circuit# 
Monitoring 
load current transformer 
 
 
#Load current transformer fault# 
Monitoring 
stack current transformer 
 
 
#Stack current transformer – 
fault# 
Monitoring 
inverter output voltage
 
 
 
#AC voltage deviation# 
Monitoring 
stack overcurrent 
X     #Stack 
overcurrent# 
Monitoring 
mains synchronisation 
 
 
#Synchronisation fault# 
Monitoring 
parallel CAN communication 
 
 
!Communication fault parallel 
CAN! 
Monitoring 
remote monitoring communication 
 
 
!Remote monitoring fault!