7.1.2 Technical 
Data 
MultiCom CCC hardware data
 
 (assembly A29.1) 
Connector :   
Port 1 RS232 for configuration 
    and 
COM 
server 
connection 
    X2: 
9-pin 
D-sub 
(socket; 
insulated) 
 
 
 
 
Port 2 RS232/RS485 for Modbus 
    X5: 
9-pin 
D-sub 
(socket; 
insulated) 
RS485 connection:   
Twisted pair with Data+, Data-, 
    shielded, 
shield 
attached 
on 
one 
side 
Distance: 
 
 
1200 m max. at 9600 baud 
Bus stations:   
Max. 32 
Data line: 
 Shielded 1:1 data line 
(2 x 0.22; twisted pair), 
e.g. Lapp "UNITRONIC-BUS LD" 
 
 
 
 
Port 3 CAN bus for remote panel 
    X4: 
3-pin 
Combicon 
connector 
 
Communication data port 1 (X2) 
Protocol: 
  CBSER 
Transmission rate: 
 
1200 - 57,600 baud (adjustable) 
Transmission parameters:  9600 baud, 8, E, 1 (default
Configuration mode:  9600 baud, 8, N, 1 
 
Communication data port 2 (X5) 
Protocol: 
  Modbus 
Transmission mode:   
Half-duplex 
Transmission code:   
RTU 
Transmission rate: 
 
1200 - 57,600 baud (variable) 
 
 
 
 
19,200 baud (default
Start bits: 
 
 
1 
Data bits: 
 
 
Parity: 
   none, 
even, odd (variable) 
Stop bits: 
 
 
2 with no parity, 1 with parity 
Function code: 
 
03 (read register) 
    06 
(write 
register) 
    16 
(write 
multiple 
registers) 
Min. response time of slave: 0-99 ms variable (0 ms default
Modbus slave address: 
01-99 (adjustable) (01 default
 
Communication data port 3 (X4) 
Protocol: 
  Proprietary 
CAN 
bus 
Transmission rate: 
 
50 kbaud