Technical specificaTions
General
User interface
Graphical LCD with blue backlight and text in  
English, French, German, Russian and Spanish
LEDs
Four status-indicating LEDs
Topology
True online, double-conversion
Diagnostics
Full system self-test
UPS bypass
Automatic bypass
Rail kit
Included with all rackmount units
Electrical Input
Nominal voltage
220–240V
Voltage range
up to 120–276 VAC (depending on load level)
Frequency range
40–70 Hz (50/60 Hz)
Electrical Output
Power factor
0.9
Voltage
±3 % of nominal regulation (on utility and battery)
Frequency regulation
±3 Hz online
Load crest factor
3 to 1
Eaton 9130 UPS
Communications
Ports
RS-232 and USB HID port as standard
Relay output
Common alarm standard
Optional communication 
cards (BD/MS Slot)
SNMP/Web card for monitoring in SNMP-based 
networks. Relay card  for remote shutdown of IBM 
AS/400 systems. MODBUS for integration to industrial 
environment.
Environmental
Safety and EMC markings IEC/EN 62040-1, IEC/EN 62040-2, CE marking
Audible noise
<50 dB
Ambient operating
0˚C to +40˚C
Storage temperature
-20˚C to +40˚C with batteries and  
-25˚C to +55˚C without batteries
Relative humidity
5–90% non-condensing
Description
Part number
Rating (VA/Watts)
Input connection
Output receptacles
Dimensions H x W x D, mm
Weight, kg
Tower Models
PW9130i700T 
103006433-6591
700/630
C14
(6) C13
230 x 160 x 350
12.2
PW9130i1000T-XL 
103006434-6591
1000/900
C14
(6) C13
230 x 160 x 380
14.5
PW9130i1500T-XL 
103006435-6591
1500/1350
C14
(6) C13
230 x 160 x 430
19.0
PW9130i2000T-XL 
103006436-6591
2000/1800
C14
(8) C13, (1) C19
325 x 214 x 410
34.5
PW9130i3000T-XL 
103006437-6591
3000/2700
C20
(8) C13, (1) C19
325 x 214 x 410
34.5
PW9130i5000T-XL
103007841-6591
5000/4500
Hardwire
Hardwire
574 x 244 x 542
75.5
PW9130i6000T-XL
103007842-6591
6000/5400
Hardwire
Hardwire
574 x 244 x 542
75.5
Tower Extended Battery Modules
PW9130N1000T-EBM 
103006438-6591
NA
NA
NA
230 x 160 x 380
18.5
PW9130N1500T-EBM 
103006439-6591
NA
NA
NA
230 x 160 x 430
24.3
PW9130N3000T-EBM 
103006440-6591
NA
NA
NA
325 x 214 x 410
50.0
PW9130N6000T-EBM
103007843-6591
NA
NA
NA
574 x 244 x 542
111
Rack Models
PW9130i1000R-XL2U 
103006455-6591
1000/900
C14
(6) C13
86.5 x 438 x 450
16
PW9130i1500R-XL2U 
103006456-6591
1500/1350
C14
(6) C13
86.5 x 438 x 450
19
PW9130i2000R-XL2U 
103006457-6591
2000/1800
C14
(8) C13, (1) C19
86.5 x 438 x 600
29
PW9130i3000R-XL2U 
103006463-6591
3000/2700
C20
(8) C13, (1) C19
86.5 x 438 x 600
29.5
Rack Extended Battery Modules
PW9130N1000R-EBM2U 
103006458-6591
NA
NA
NA
86.5 x 438 x 450
22.1
PW9130N1500R-EBM2U 
103006459-6591
NA
NA
NA
86.5 x 438 x 450
28.1
PW9130N3000R-EBM2U 
103006460-6591
NA
NA
NA
86.5 x 438 x 600
41.1
BATTERY RUNTIMES*
Internal batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
75% Load
50% Load
75% Load
50% Load
75% Load
50% Load
75% Load
50% Load
75% Load
50% Load
Rack models
PW9130i1000R-XL2U
13
22
55
82
103
186
151
250
223
312
PW9130i1500R-XL2U
11
18
47
81
83
143
126
208
195
262
PW9130i2000R-XL2U
13
24
63
95
118
190
170
242
221
345
PW9130i3000R-XL2U
8
14
34
62
70
92
96
156
130
211
Tower models
PW9130i700T-XL
12
19
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PW9130i1000T-XL
13
22
55
82
103
186
151
250
223
312
PW9130i1500T-XL
11
18
47
81
83
143
126
208
195
262
PW9130i2000T-XL
21
34
81
130
145
198
184
293
248
431
PW9130i3000T-XL
12
20
49
79
90
143
134
180
165
240
PW9130i5000T-XL
20
34
81
136
153
232
217
328
273
477
PW9130i6000T-XL
16
27
66
107
120
194
178
267
231
372
1. Multilingual graphical LCD
display
2. Panel for replacing batteries
3. 1 USB port + 1 serial port
4.
1 Relay Output + 1 EPO
connector
5. EBM battery unit connector
6. Load segments
7.  Communication card slot
1
2
2
3
5
7
6
© 2011 Eaton Corporation, All Rights Reserved, 00DATA1018094 rev D, December 2011
* Runtimes are shown at a 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
1
6
4
3
7
4
In the interests of continuous product improvement all specifications are subject to change without notice.
www.eaton.com/powerquality