9.  Position And Velocity Pointers 
If all local motors have digital quadrature encoders (1-line ECT entries), and no other entries are used 
in  the  Encoder  Conversion  Table  then  the  position  (Ixx03)  and  Velocity  (Ixx04)  pointers  of  the 
MACRO motors are valid by default (set by firmware) and need not be changed: 
 
MACRO 
motor 
Motor # 
Ixx03, Ixx04 
 
MACRO 
motor 
Motor # 
Ixx03, Ixx04 
1
st
 
5 or 9 
$350A 
 
5
th
 
9 or 13 
$3512 
2
nd
 
6 or 10 
$350C 
 
6
th
 
10 or 14 
$3514 
3
rd
 
7 or 11 
$350E 
 
7
th
 
11 or 15 
$3516 
4
th
 
8 or 12 
$3510 
 
8
th
 
12 or 16 
$3518 
 
However, if the Encoder Conversion Table has been modified then the MACRO motors/nodes entries 
need to be configured properly. This can be  done using the Encoder Conversion Table utility  in the 
PewinPro2 under Configure>Encoder Conversion Table: 
 
 
 
Click on End of Table to access the next available entry 
 
Conversion Type: Parallel position from Y word with no filtering  
 
No Shifting 
 
Width in Bits: 24 
 
Source Address: Servo node Address (See table below) 
 
Record the processed data address.  
This is where the position and velocity pointers will be set to for a specific node/motor number. 
E.g. I903,2=$351A  
 
Repeat steps for additional motors/servo nodes