Pinouts and Software Setup 
 32 
Magnetic Contactors 
 from 
 or similar contactor can be used. 
 
Line Filters 
Line filters eliminate electromagnetic noise in a bi-directional manner (from and into the system). 
T type filters are NOT recommended. PI type line filters are highly advised: 
 
Filter should be mounted on the same panel as the drive and power source. 
 
Filter should be mounted as close as possible to the power source. 
 
Filter should be mounted as close as possible to incoming cabinet power. 
 
 from 
 or similar filter can be used. 
 
Voltage Suppressors 
Voltage suppressors eliminate undesirable voltage spikes typically generated by the magnetic contactor or 
external machinery in the plant.  
This 3-phase 
 from 
 or similar suppressor can be used. 
 
Bus Power Cables 
The Geo Brick Drive electronics create a DC bus by rectifying the incoming AC lines. The current flow 
into  the  drive  is  not  sinusoidal  but  rather  a  series  of  narrow,  high-peak  pulses.  Keeping  the  incoming 
impedance small is essential for not hindering these current pulses. 
Whether  single-  or  three-phase,  it  is  important  that  the  AC  input  wires  be  twisted  together  to  eliminate 
noise radiation as much as possible. Recommended wire gauge: 
 
Model 
Wire Gauge 
(AWG) 
 
Model 
Wire Gauge 
(AWG) 
GBL4-xx-5xx 
12 
 
GBL8-xx-552 
10 
GBL4-xx-8xx 
10 
 
GBL8-xx-882 
GBL6-xx-5xx 
 
GBL8-xx-582 
GBL6-xx-8xx 
 
GBL8-xx-852 
 
 
Note 
All  ground  conductors  should  be  8AWG  minimum  using  wires 
constructed  of  many  strands  of  small  gauge  wire.  This  ensures  the 
lowest impedance to high-frequency noises.