Step1 : Choose Max PFM clock by changing the PFM clock divider in the calculator
Step2 : Choose PFM Pulse Width by changing I7m04 in the calculator
For a PFM clock range 0-20 KHz, and a pulse width of ~20 μsec:
Step2 : Choose PFM Pulse Width by changing I7m04 in the calculator
For a PFM clock range 0-20 KHz, and a pulse width of ~20 μsec:
I6803=2290
; PFM Clock divider equal to 6
I6804=13
; PFM Pulse Width Control equal to 13
The output frequency control Ixx69 specifies the maximum command output value that
corresponds to the maximum PFM Frequency.
I6826=3
; MACRO IC0 Channel2 Output Mode Select. C PFM
M8000->Y:$7841C,8,16,S ; Supplementary Channel 2* Output C Command Value
; Min=0, Max= Calculated Ixx69
Testing The PFM Output
Writing, directly to the suggested M-variable (i.e. M8000), values proportional to Ixx69
produces corresponding frequencies:
produces corresponding frequencies:
M8000 PFM [KHz]
0
0
1213
11
2427
22