485SDA103798 Manual
B&B Electronics  --  707 Dayton Rd.  --  PO Box 1040  --  Ottawa, IL  61350
PH (815) 433-5100  --  FAX (815) 434-7094
Set Digital Output Command
The Set Digital Output command is used to set the states of the
3 digital output lines.  This command requires a data byte.  The data
byte is used to specify the output states.  Bits 0-2 correspond to the
states of digital outputs 0-2.  If a bit is a 0 then the output will be set
LOW. If a bit is a 1 then the output will be set HIGH. Refer to Table
3.6.  NOTE: This command ignores Bits 3-7 of the data byte.
Command Syntax
!{addr}SO{states}
Where {states} is a byte in which Bits 0-2 correspond to the outputs
states of Digital Outputs 0-2
Unit Response
no response
Set Module Address Command
The Set Module Address command is used to change the
address of a 485SDA10. This command requires a data byte. The
data byte is used to specify the new address of the unit. The
address of a module is stored in non-volatile memory.
Command Syntax
!{addr}SA{new address}
Response Syntax
no response
Where {addr} is the current address of the module and {new
address} 
is a byte representing the new address.
Table 3.6 - Set Digital Output Data Byte Values
Data Byte
Digital Outputs
Bit 2
Bit 1
Bit 0
#2
#1
#0
0
0
0
LOW
LOW
LOW
0
0
1
LOW
LOW
HIGH
0
1
0
LOW
HIGH
LOW
0
1
1
LOW
HIGH
HIGH
1
0
0
HIGH
LOW
LOW
1
0
1
HIGH
LOW
HIGH
1
1
0
HIGH
HIGH
LOW
1
1
1
HIGH
HIGH
HIGH