9-6
 • 
E2 RX/BX/CX I&O Manual 
9.1.3
Input Setup in E2
At this point in the setup process, you should have all 
sensors, transducers, and other input devices wired to 
points on MultiFlexes, 16AIs, and all output devices con-
nected to 8ROs, 8DOs, or 4AOs outputs. Once the physi-
cal wiring is complete, you will need to tell E2 the types of 
sensors or devices that are connected to each I/O point. 
This is achieved in the Input and Output Definitions 
screens.
9.1.3.1
Configuring a Point from the 
Input Definitions/Status Screen
To configure a point, go to the Input Definitions/Status 
screen by pressing Alt + I or:
1.
Press 
 to open the Main Menu
2.
Press 
 (System Configuration)
3.
Press 
 (Input Definitions)
The Input Status screen opens:
Figure 9-4
 - Input Status Screen
Use the up and down arrow keys to move the cursor to 
the point you wish to set up, and press 
 (SETUP).
A pop-up menu such as the one shown in Figure 9-5 
will prompt you to specify the point as analog or digital. 
Press 
 if the input is analog, press 
 if the input is dig-
550-2500 
550-2550 
KW Transducer
Down for 4-
20mA, Up for 
Pulse
4-20 mA output to input board
1.
Wire positive transducer terminal 
to positive 24VDC supply.
2.
Wire negative transducer termi-
nal to odd numbered input termi-
nal.
3.
Wire negative 24VDC supply to 
even numbered input terminal.
4.
Place 250
 resistor across odd 
and even numbered input termi-
nals.
Pulse Accumulator output to input board
1.
If the input board is an 8IO or a 16AI version 
E.02 or greater, connect the two KWh terminals 
to the input point (polarity insensitive)
2.
If the input board is a 16AI version less than 
E.02, connect the KWh terminals to board point 
1. Set input switch #1 DOWN, and set input 
switch #8 UP.
3.
If the input board is a 16AIe, connect the two 
KWh terminals to input # 1, 2, 3, or 4 ONLY.
P/N
Sensor
Input Type
Dip Switch
Wiring
Table 9-1
 - Sensor Wiring