Emerson E2 Manuel D’Utilisation

Page de 283
Case Control Circuits
Software Overview
 • 
11
-
15
Clean Modes may be either fixed or timed. Fixed 
Clean Modes begin when the clean switch is turned ON 
and end when the clean switch is turned OFF. Timed Clean 
Modes begin when the clean switch is turned ON and ends 
a specific time afterwards. The user specifies how long the 
wash mode will last.
End of Mode Warning
To warn service personnel that wash mode is about to 
end, the case controller will blink the case lights for five 
seconds. After five seconds of blinking, the case fan will 
activate and refrigeration will restart.
11.4.10 Walk-In Freezer Control
The CC-100P and CCB (dual-pulse valve model) case 
controller is used to control walk-in boxes, since it is the 
only model capable of controlling two valves.
Walk-in boxes are controlled the same way as for other 
cases. The primary difference between walk-in boxes and 
other cases is the use of the door switch.
When the case controller’s door switch input is turned 
ON, refrigeration is suspended (all pulse valves go to 0%), 
the fans turn OFF, and the lights turn ON. The walk-in box 
remains in this state until the door switch turns OFF again.
Alarm times can be assigned to the door switch input 
so that an alarm can be generated when the door is left 
open for too long. 
Also, when temperature alarm setpoints are configured 
for the case, the case controller will begin refrigeration if a 
temperature alarm trips with the door open.
11.4.11 Fail-Safe Mode
When major system malfunctions occur, the case con-
troller enters a Fail-Safe Mode. The Fail-Safe Mode is 
designed to keep the case functioning as normally as pos-
sible under system conditions that would otherwise make 
case control impossible.
A case controller will enter Fail-Safe Mode whenever 
one of three conditions occur:
1.
The superheat and/or temperature control set-
point(s) are corrupted (i.e., outside of its pro-
grammed minimum/maximum range).
2.
The software is corrupted.
3.
An unrecoverable sensor failure has occurred 
(see Operation with Failed Sensors, below).
Actions Taken During Fail-Safe Mode
When a case controller enters Fail-Safe Mode, each 
output will be set to the fail-safe state described in 
Table 11-7 - Fail-Safe States
Output
Fail-Safe State
Pulse Valve, Stepper Valve
Controller will fix 
the position to the 
last known good out-
put percentage
Fans
ON
Lights
ON
Defrost
OFF
Anti-Sweat
Pulse at 50%
CC-100 and CS-100 Alarm 
LEDs (red)
Flashes at a rate of 2 
per second
Dual Temp Output
Off
Suction Solenoid Valve
Open
Liquid Solenoid Valve
Open
Satellite Output(s)
OFF
11.4.11.1 Recoverable Sensor Failures
The CC-100 and CS-100 will be able to cope with 
some sensor failures without having to enter Fail-Safe 
Mode.
Coil In or Coil Out Failure
A coil inlet temperature or coil outlet temperature sen-
sor will be considered failed if one of two conditions 
occur:
1.
The sensor gives a value outside of its minimum 
and maximum temperature range (that is, below -
50°F or above 120°F) for two consecutive read-
ings, or
2.
The sensor value is 20°F above the control set-
point for longer than ten minutes.
 If the coil inlet or coil outlet temperature sensor has 
failed, the case controller will compensate by “guessing” 
the inlet or outlet temperature based on the values of the 
remaining functional coil sensor and the case temperature 
sensor(s). The case controller will continue to guess the 
value until the coil inlet or outlet sensor can be fixed.
If both the coil inlet and coil outlet sensors have failed, 
or if one coil sensor and the case temperature sensor(s) 
have failed, the case controller will not be able to make the 
required calculations, and they will go into Fail-Safe 
Mode.
Discharge/Return Air
If the sensor or combination of sensors supplying the 
case temperature to the case controller have failed (i.e., the