11-18
 • 
E2 RX/BX/CX I&O Manual 
matically. 
When you first create an application in the E2, you can 
tell which inputs and outputs belong to the Base Log 
Group: an “L” will be displayed at the right-hand side of 
their definitions. The “L” is a marker that signifies that the 
input or output is currently part of a logging group (either 
the Base Log Group or another group as assigned by the 
user). If there is no “L” beside the definition, the value is 
not part of a logging group and therefore will not be 
logged.
11.5.4 Setting Up Logging
To begin logging setup, go to the Logging Setup menu:
1.
Press 
 for the Main Menu.
2.
Press 
 System Configuration.
3.
Press 
 Logging Setup.
Figure 11-8
 - Logging Setup Menu
From this menu, you can control different logging 
aspects:
• Access Log Group summary screen (or Base Log if 
no additional log groups exist) to set logging 
parameters
• Add a new log group and automatically enter edit 
mode
• Delete a log group
• Displays a report of all logged points for the entire 
system
For Base Log setup, select 1. Log Groups from this 
menu:
Figure 11-9
 - Summary Screen for Logging Groups
The summary screen for Logging Groups will open 
where a variety of log parameters can be viewed. Log 
group name, configured resolution setting, number of days 
to keep logs, the amount of available logging resources, 
number of analog and digital points associated with this 
logging group, status, and more can all be seen from this 
summary screen.
 
Highlight the desired logging group and press 
 
to open the setup screen for that log group:
Figure 11-10
 - Logging Setup
From this screen, logging group configuration can be 
specified. Group name, interval between log records, 
mode, start date and time, duration of logs, log resolution, 
points, percentage used, status, and enable/disable logging 
can be configured. (See the online help for each property 