E2 RX/BX/CX I&O Manual 
11.6.11 Separate Setpoints
The Separate Setpoints strategy for AHU allows a Cut 
In/Cut Out setpoint to be set up for each heat and cool 
stage instead of just one cool and one heat setpoint set up 
for each stage (Normal strategy). Dehumidification con-
trol can be performed while controlling with separate set-
points.
11.6.12 AHU Zone Control
Unlike MultiFlex RTU rooftop controller applications, 
AHU applications are not required to be grouped into 
Zone applications (AHUs are usually large enough to be 
“zones” in and of themselves). 
However, if desired, you may associate an AHU Con-
trol application with a Zone application. The AHU will 
then use the Zone’s Temperature Control setpoints, occu-
pancy state, summer/winter state, and economization and 
dehumidification enable signals. More information on 
Zone control is available in Section 11.7, Zone Control
11.6.13 Hardware Overview
To set up an AHU for control by an E2, numerous tem-
perature and humidity sensors for several different appli-
cations must be connected to the I/O Network, as well as 
fan and cool proof checking devices, economization 
checking devices, curtailment devices, and all of the heat-
ing, cooling, and dehumidification outputs. 
Listed below are wiring instructions for some of the 
inputs and outputs that are part of a typical AHU setup.
Table 11-10
 - Suction Group Inputs
Inputs
Sensor Type
Wiring 
Instructions
Space Temperature
Temperature
Space Humidity
Humidity
Supply Air Temp
Temperature
Return Air Temp
Temperature
Outdoor Air Temp
Temperature
Set up as Out-
door Air Provider 
in Global Data 
(see 
).
Outdoor Air Humid
Humidity
Set up as Out-
door Humidity 
Provider in 
Global Data (see 
).
Curtailment Device
Digital
Set up as Curtail-
ment in Global 
Data (see 
Fan Proof
Digital 
Fan Proof Reset
Digital
VS Inverter Alarm
Digital
Enthalpy Switch 
(Indoor and/or Out-
door)
Digital
Dewpoint Probe (for 
Economization)
Dewpoint
Mixed Air Temp (ana-
log economizers only)
Temperature
Inputs
Sensor Type
Wiring 
Instructions
Table 11-10
 - Suction Group Inputs