Emerson E2 Manuel D’Utilisation

Page de 283
11-36
 • 
E2 RX/BX/CX I&O Manual 
integral) of the demand window. The integral error rep-
resents how far below or above the setpoint the input has 
been for the entire demand window.
Under non-demand conditions, the integral error will 
be below zero, since the average KW or watt-hour value 
will be below the setpoint.
The current value of the integral error and the current 
value of the KW input are what determine when the 
Demand Control application will begin load shedding. 
11.11.3 Load Shedding
11.11.3.1 Definition
Load shedding is the process of curbing the amount of 
kilowatt usage within one or more target applications. 
Most applications that drive mechanical or electronic 
devices, such as lights, heaters, air conditioners, compres-
sors, etc., are configured with special inputs that, when 
active, “shed” the application.
Physically, when a device is “shed,” its control set-
points are altered by a specified amount in a direction that 
will save energy. For instance, an HVAC unit with heating 
and cooling stages that is commanded to shed will have its 
heating setpoints lowered and its cooling setpoints raised. 
This will cause the HVAC unit to operate at a lower capac-
ity, thus saving energy.
Table 11-13 lists a number of E2 RX-300 and BX-300 
applications and how load shedding affects them.
Table 11-13 - Shedding Effect on Applications
Application
Shedding Effect
All HVAC applica-
tions (RT-100s, 
MultiFlex RTUs, 
AHUs, Heat/Cools)
Raises cooling setpoints, low-
ers heating setpoints
Sensor Control and 
Analog Input I/O 
Modules
Raises or lowers Cut In/Cut 
Out setpoints (whichever direc-
tion saves energy)
Refrigeration Cir-
cuits
Raises case temperature set-
points
Suction Groups
Raises suction setpoint
Condenser
Raises discharge setpoint
Analog Output I/O 
Modules
Raises or lowers PID setpoint 
(whichever will save energy)
Digital Output I/O 
Modules
Control output is locked OFF.
11.11.4 Shedding Levels
Some applications have a single input (usually called 
DEMAND SHED) that, when ON, sheds the application. 
Each application is programmed with a specific “demand 
bump” value that is added or subtracted from the control 
setpoints when this input comes ON.
 Other applications, notably HVAC applications, have 
two inputs: a primary and a secondary (usually called PRI 
DEMAND SHED and SEC DEMAND SHED). Each 
input has its own “demand bump” value, so that when the 
primary is ON, the primary demand bump is in effect, and 
when the secondary is ON, the secondary demand bump is 
in effect. When both of these inputs are ON, the demand 
bump values are added/subtracted together and applied to 
the setpoint(s). As a result, two levels of shedding are pos-
sible for a single application.
Example: An air conditioner with a cooling setpoint of 
70°F has a primary demand bump value of 2 and a sec-
ondary demand bump value of 2. In a typical Demand 
Control application setup, the PRI DEMAND SHED input 
would be one of the first inputs to go into shed; when this 
occurs, the bump value is added to the cooling setpoint, 
raising it to 72°F.
The SEC DEMAND SHED would be set up to shed 
later (if necessary) as a second level of shedding for the 
air conditioner. When this input is turned ON, the setpoint 
is raised by the secondary demand bump value. Since the 
PRI DEMAND SHED input is still ON, both values are 
added to the setpoint, raising the setpoint to 74°F.
11.11.5 Priority Levels
Each application that you wish to set up for shedding 
must be assigned a priority level in the Demand Control 
application. When a Demand Control application sheds 
loads, it does so by shedding all applications that are in the 
first priority level, and then continuing to shed higher pri-
ority levels until the demand is at an acceptable level or 
until all levels are shed.
Priority levels are simply outputs that connect to the 
demand shedding inputs of one or more applications. 
When a level is shed, the output comes ON and all appli-
cations connected to the output are shed.
There are three types of priority levels:
1. First Shed
First Shed levels are the first ones to be shed when 
demand shedding begins. The Demand Control applica-
tion first begins shedding by activating level #1 of the 
First Shed levels. As needed, each level thereafter is shed 
in succession (#2, #3, and so on to #20).
Applications that are part of the First Shed priority lev-
els should be non-vital applications that would have no 
significant effect on the system if it were to be shed for a 
prolonged period of time. Examples: motor room exhaust 
fans, satellite HVAC units and/or lights in low-occupancy