TIPS: ACKNOWLEDGEMENT VS. RESETTING
• Reset an alarm if you believe the condition that 
caused it is fixed, but you wish for a new alarm to 
occur if the problem happens again.
• You  MUST  reset an alarm that has been previ-
ously acknowledged to re-enable alarming for 
the alarm. Failure to do so will cause the alarm 
to remain in ACK, and the alarm will not be gen-
erated again. AN ACKNOWLEDGED ALARM 
WILL NOT AUTOMATICALLY RESET.
• Acknowledge an alarm to silence alarm panel 
horns or lights, ONLY IF technicians have been 
notified of the problem and have been dis-
patched. Technicians, after fixing the problem, 
MUST reset or clear the alarm to re-enable 
alarming.
12-14
 • 
E2 RX/BX/CX I&O Manual 
To acknowledge an alarm or notice, highlight the 
desired log entry and press
 
 (ALARM ACK). A 
screen will come up prompting the user to either acknowl-
edge the selected advisory, acknowledge all advisories, or 
to cancel the operation. 
• Press
 
 
to acknowledge the selected advisory. 
• Press 
 to acknowledge all advisories. 
• Press 
 to cancel the operation. 
12.10.8.2 Resetting
When a log entry is reset, it is forced to a normal con-
dition and the log entry remains in the Controller Advisory 
Log.
An alarm, notice, or failure can be reset by highlight-
ing a log entry and pressing 
 (ALARM RST) while at 
the Advisory Log screen. A screen will come up prompt-
ing the user to either reset the selected advisory, reset all 
advisories or to cancel the operation. 
1.
Press 
 to reset the selected advisory.
2.
Press 
 to reset all advisories.
3.
Press 
 to cancel the operation.
12.10.8.3 Clearing
The option to clear logs completely removes a log 
entry from the Advisory Log.
Advisory Log entries may be cleared by highlighting 
the log entry and pressing 
 (ALARM CLR) while 
viewing the Advisory Log screen. A screen will come up 
prompting the user to either clear the selected advisory, 
clear all advisories or to cancel the operation. 
1.
Press 
 
to clear the selected advisory. 
2.
Press 
 to clear all advisories.
3.
Press 
 to cancel the operation.Expanded Advi-
sory Information
Figure 12-22
 - Expanded Info Screen
To view expanded information on a log entry, highlight 
the desired log and press 
 (EXPD INFO). A screen 
will come up telling the user what advisory is being 
viewed out of a total number of advisories. 
Property or Board/Point 
This message shows the location where the advisory 
was generated. This will be a board and point address or 
an application input or output (in Area Ctrl:Applica-
tion:Property) format.
Advisory Message
The advisory message is displayed below the Property 
or Board/Point. The Advisory Message describes the advi-
sory log entry (what went wrong in the system). 
Acknowledge Status
Acknowledge Status describes the state of the advi-
sory. If an advisory has been acknowledged or reset, the 
user name or the person who acknowledged or reset the 
alarm will appear below the acknowledge status. The date 
and time when the advisory was acknowledged or reset 
will also be displayed below the user’s name.
If the advisory has not been acknowledged or reset, 
this field will display an asterisk “*” along with the word 
“UNK.”
Report Priority
The report priority fields describe the priority level of 
the advisory, as well as the date and time the advisory 
occurred. 
Return To Normal
If the advisory has returned to a normal state, either on 
its own or because of a user-ordered alarm reset, the date