Appendix A: Case Type Defaults
 • 
A
-
1
Appendix A: Case Type Defaults
The table below lists the sixty-four default case types 
that may be used in Standard Circuit or Case Control Cir-
cuit applications along with the recommended defaults for 
each case type. 
When one of these sixty-four case types is selected, the 
E2 automatically enters the following information from 
the table into the Circuit application:
• The setpoint
• The number of defrosts per day and the defrost time 
length from the “Elec” column under Defrost types 
For example, if you select #14 “RIFF” (reach-in frozen 
food), the E2 sets the circuit’s setpoint at -10, the number 
of defrosts at 1, and the defrost time at 60 minutes.
The other columns in this table, such as the High and 
Low Alarm/Dly columns and the Hot Gas, Rev. Air, and 
Timed columns, are suggested values that are not automat-
ically entered into the Circuit application.
High Alarm, Low Alarm, and Delay
The High Alarm, Low Alarm, and Delay columns are 
the suggested high and low case temperature alarm set-
points and the report delay. To set up these alarm setpoints 
and delays, locate the Case Temperature control input and 
select the Generic Alarm Setup action from the Actions 
Menu. Enter the High and Low setpoints in the Normal Hi 
and Normal Low fields respectively. Enter the Delay in the 
Report Delay field.
Defrost Type
The E2 assumes by default that all cases have electric 
defrost. If this is not the case, you will have to enter new 
values for the Number of Defrosts and the Defrost Time in 
the circuit. The suggested defaults are listed under the Hot 
Gas, Elec, Rev. Air, and Timed columns. The number to 
the left of the slash indicates the suggested number of 
defrost times per day, and the number to the right of the 
slash indicates the recommended Defrost Time length.
Defrost Type
Type
Abbr.
Description
Set-
Point
High 
Alarm
Low 
Alarm
Delay
Hot Gas
Elec.
(DEF)
Rev. Air
Timed
0 ****
Undefined
1 SDIC
Single deck ice cream
-25
-5°
-30°
01:00
2/18
1/45
1/60
1/60
2 MDIC
Multi-deck ice cream
-25
-5°
-30°
01:00
3/22
3/45
2/60
2/60
3 SDFJ
Single deck freezer juice
-18
-30°
01:00
2/18
1/45
1/60
1/60
4 MDFJ
Multi-deck freezer juice
-10
-25°
01:00
3/22
3/45
2/60
2/60
5 RIIC
Reach-in ice cream
-15
-5°
-25°
01:00
2/22
1/45
1/60
1/60
6 ICBX
Ice cream freezer box
-20
-5°
-30°
01:00
3/20
2/45
2/60
2/60
7 SDFF
Single deck freezer food
-15
-25°
01:00
2/18
1/60
1/60
1/60
8 RIFJ
Reach-in freezer juice
-15
-5°
-20°
00:15
2/22
1/45
1/60
1/60
9 FRBX
Frozen food box
-12
-5°
-20°
00:15
3/18
3/45
2/60
2/60
10 FFBX
Frozen fish box
-12
-5°
-20°
00:15
3/18
3/45
2/60
2/60
11 FJBX
Frozen juice box
-12
-5°
-25°
01:00
3/18
3/45
2/60
2/60
12 MDFF
Multi-deck freezer food
-10
-20°
01:00
2/22
1/45
2/60
2/60
13 FZBK
Multi-deck freezer bakery
-10
-20°
01:00
2/22
1/45
2/60
2/60
14 RIFF
Reach-in freezer food
-10
-15°
01:00
1/20
1/60
1/60
1/60
15 SDMT
Single deck meat
22
32°
12°
01:00
3/18
3/45
3/60
3/60
16 SDPF
Single deck prepared
22
32°
12°
01:00
3/18
3/45
3/60
3/60
17 PZZA
Single deck pizza
22
32°
12°
01:00
3/18
3/45
3/60
3/60
18 KOSH
Single deck kosher
22
32°
12°
01:00
3/18
3/45
3/60
3/60
19 SDFH
Single deck fish
22
32°
12°
01:00
3/18
3/45
3/60
3/60
20 MDMT
Multi-deck meat
23
34°
18°
01:00
4/18
4/45
4/60
4/60
21 MDPO
Multi-deck poultry
23
34°
18°
01:00
4/18
4/45
4/60
4/60
22 MDFH
Multi-deck fish
23
34°
18°
01:00
4/18
4/45
4/60
4/60
23 RIMC
Reach-in meat
25
35°
15°
01:00
2/18
2/45
2/60
2/60
24 SVMT
Service meat
22
35°
15°
01:00
2/18
2/45
2/60
2/60
25 SVFH
Service fish
22
35°
15°
01:00
2/18
2/45
2/60
2/60
26 MTBX
Meat cooler
30
42°
22°
01:00
3/18
3/45
2/60
2/60
Table A-1
 - Case Type Default Settings