Emerson E2 Manuel D’Utilisation

Page de 283
6-8
 • 
E2 RX/BX/CX I&O Manual 
The meter is housed in a plastic enclosure suitable for 
installation on T35 DIN rail according to EN50022. The 
Energy Meter can be mounted with any orientation over 
the entire ambient temperature range, either on a DIN rail 
or in a panel. The meter is not sensitive to CT orientation 
to reduce installation errors.
6.3.5.2
Supported System Types
The Energy Meter Series has a number of different 
possible system wiring configurations. To configure the 
meter, set the System Type via the User Interface or Mod-
bus register 130 (if so equipped). The System Type tells 
the meter which of its current and voltage inputs are valid, 
which are to be ignored, and if neutral is connected. Set-
ting the correct System Type prevents unwanted energy 
accumulation on unused inputs, selects the formula to cal-
culate the Theoretical Maximum System Power, and deter-
mines which phase loss algorithm is to be used. The phase 
loss algorithm is configured as a percent of the Line-to-
Line System Voltage (except when in System Type 10) 
and also calculates the expected Line to Neutral voltages 
for system types that have Neutral (12 & 40).
For more information about this application, see the 
Energy Meter manual (P/N 026-1726).
6.3.6
Modular Refrigerant Leak 
Detection Sensor (MRLDS) 
Figure 6-6
 - MRLDS
The Modular Refrigerant Leak Detection Sensor 
(MRLDS) continuously monitors for low levels of refrig-
erants most commonly used in commercial refrigeration 
systems.
The MRLDS communicates with the E2 controller via 
MODBUS. The E2 will provides an interface while the 
MRLDS will provide the leak monitoring functionality.
6.3.7
Copeland Discus with 
CoreSense Protection 
Figure 6-7
 - Copeland Discus Compressor
The Discus application can monitor semi-hermetic 
compressors using the MODBUS network on E2 versions 
3.01 and above. The E2 monitors and records semi-her-
metic compressor information. The Discus application has 
extensive logging capabilities that record a compressor’s 
Run History, Fault History, and Alarm Status.
The Copeland Discus is supported on E2 RX-300, CX-
400 and above. 
6.3.8
Copeland CoreSense 
Communications
Figure 6-8
 - Copeland CoreSense Communications
CoreSense Communications is used on A/C scroll 
compressors in the E2. The CoreSense Communications 
application provides the user interface requirements for 
configuration setup, status display, and alarm handling. 
CoreSense monitors information on the compressor's 
operation and sends it to the controller, and can also moni-
tor conditions inside the compressor to prevent compres-