Open Echelon Device Connectivity
Echelon Network and Hardware Setup
 • 
8
-
5
lers)
Enter the number of Echelon devices you wish to add 
on the Connected I/O screen:
Figure 8-5
 - Connected/IO Setup Screen (RX Unit Shown)
Navigate to the Open Echelon field under the Third 
Party Tab section of the Connected I/O setup screen and 
enter the number of Echelon devices to be added.
Next, commission the Echelon device. Commissioning 
is done at the Controller Setup screen. If still on the Con-
nected I/O screen, hit the back button to go back to the 
Network setup menu and select 
 
(Controller Setup). Or, 
from the Main Menu:
1.
 Select
 
 (System Configuration)
2.
 Select
 
 
(Network Setup)
3.
 Select
 
 
(Network Summary)
Commission the device on the Network Summary 
screen:
Figure 8-6
 - Network Summary Screen (RX Unit Shown)
Highlight the LonMark device on the screen you wish 
8.8.1.1
Troubleshooting
After commissioning has been completed, check to 
make sure the device has been added successfully. From 
the Main Menu, select
 
 (Configured Applications) to 
open the Configured Applications list. If the device you 
have commissioned does not appear in this list, the 
Description File has failed to upload correctly onto the E2. 
An alarm of No Description File will be generated and 
can be found in the Alarm Advisory Log. Call Emerson 
Retail Solutions at 770-425-2724 to contact your sales rep-
resentative or technical assistance to obtain the Descrip-
tion File.