The 16AI, 8IO, and MultiFlex Inputs
Input and Output Setup
 • 
9
-
1
9
Input and Output Setup
9.1
The 16AI, 8IO, and 
MultiFlex Inputs
9.1.1
Connecting Sensors to Input 
Boards
There are five I/O Network boards that may accept 
inputs: the MultiFlex, the 16AI, the ARTC, and the 8IO 
Combination Input/Output Board. Wiring an input to these 
boards requires three steps:
1.
Connect the sensor’s signal wires to the two ter-
minals of an input point.
2.
Set the input type dip switch that corresponds to 
the point being connected.
3.
If necessary, connect the power lead of the sensor 
to one of the 5V or 12V power terminals.
9.1.1.1
Wiring
MultiFlex Boards
An input point connector on a MultiFlex, 16AI, and 
16AIe board consists of two terminals, as shown in Figure 
9-1
. One of these terminals, labeled “SIG”, reads the sig-
nal from the sensor, while the other, labeled “0v” is where 
sensor’s ground and/or cable shield wire is connected.
Figure 9-1
 - Input Board Points
16AI Boards
On a 16AI, terminals are numbered 1-32, starting with 
the first terminal of point 1 and ending with the last termi-
nal of point 16. The even-numbered terminals of a 16AI 
are always where the signal voltages are connected. The 
sensor grounds and cable shields are connected to the odd-
numbered terminals.
8IO and ARTC Boards
On an 8IO board, the two terminals of every point are 
labeled “-” or “+”. The ground wire is always connected to 
the “-” terminal, and the signal wire is connected to the 
“+” terminal.
On the ARTC board, the input and output points are 
predefined and are labeled accordingly.
9.1.1.2
Sensor Wiring Types
Specific wiring types are required for each type of sen-
sor used with E2. 
All Analog Temperature Sensors and Air Flow Sen-
sors
Temperature and air flow sensors are to be wired with 
shielded, 2 conductor, at least 22 GA wire (Belden # 8761 
or equivalent).
All Pressure Transducers, Humidity Sensors, and 
Refrigeration Transducers
Pressure and refrigeration transducers and humidity 
sensors are to be wired with shielded, 3 conductor, at least 
22 GA wire (Belden #8771 or equivalent).
Dewpoint and Light Level Sensors
These sensors are to be wired with shielded, 4 conduc-
tor at least 22 GA wire (Belden # 8729 or equivalent).
9.1.1.3
Input Type Dip Switches
An input type dip switch must be set for each input 
point. Input type dip switches are located in the switch 
banks labeled S1 and S2 on the MultiFlex, 16AI, and 
switch bank S4 on the 8IO.
The input type dip switch tells the input board whether 
or not the sensor connected to the point requires a DC sup-
ply voltage in order to operate. If the sensor requires DC 
voltage, the dip switch should be set to the DOWN posi-
tion. If the sensor does not require power, or if it uses AC 
power, the dip switch should be set to the UP position. Dip 
switches for unused points should be set to the UP posi-
tion.
The dip switch positions for each specific sensor type 
is shown in Figure 9-2.