2 en | Legal  
F220 Series Detectors with F220-B6/C/E/R Bases
4998138694 -04 | 2007.01
Installation Manual
Bosch Security Systems, Inc.
1
Legal
1.1
Trademarks
CleanMe
®
 is a registered trademark of GE Interlogix in the 
United States and/or other countries.
Chamber Check
®
 is a registered trademark of Bosch Security 
Systems, Inc. in the United States.
Chambermaid™ is a trademark of Bosch Security Systems, Inc. 
in the United States.
ENVI-RO-TECH™ is a trademark of Tech Spray L.P.
TECHSPRAY
®
 is a registered trademark of Tech Spray L.P.
1.2
Required Maintenance and Testing
Keep the detector calibrated for proper operation. NFPA 72, 
The National Fire Alarm Code, recommends performing 
calibration tests at installation, then every other year. 
Depending on local regulations, calibration testing might be 
required more than once a year.
Perform functional testing yearly.
Test the calibration (to meet NFPA 72) using either the magnet 
test or measuring the calibration with a calibrated product from 
No Climb Products Ltd. Quickly determine the calibration by a 
visual inspection of the detector’s LED (refer to Section 4.4 
Flash Rate and Trouble Indication on page 22). These tests 
confirm whether or not the detector is within its factory marked 
calibration range.
At least once a year vacuum or wipe the external part of the 
detector clean. Pay particular attention to the detector screens 
in areas of heavy insect activity or dust. To clean the chamber, 
i
NOTE! Notify all concerned parties before any 
maintenance or testing of the fire alarm system and upon 
completion of these activities.