Prepare the Burner
 General
   In most cases, the burner is ready to mount to the 
appliance.  There can be situations where the burn-
er needs to be reconfi gured to perform properly in 
the appliance.  Review the appliance manufactur-
er’s  specifi cations prior to installing to determine if 
any modifi cation is required to properly confi gure 
the burner. 
  Instruction on how to perform the following burner 
preparation  tasks can be found in the Professional 
Maintenance section.
Remove / install burner nozzle
Check head/air adjusting plate
Low Firing Rate Baffl e (If specifi ed)
  The NX Low Firing Rate Baffl e (LFRB), refer to Fig-
ure 2, reduces the burner airfl ow and pressure. Re-
fer to the appliance manufacturer’s instructions or 
the Beckett OEM Specifi cation Guide part number 
6711. To avoid poor burner performance, do not 
omit the baffl e when specifi ed or install the baffl e 
when not specifi ed. 
Note: 
  The Low Firing Rate Baffl e may have been factory 
installed. If fi eld installation is required, insert the 
Low Fire Rate Baffl e into the housing, aligning the 
mounting screw hole with the notched hole in the 
burner housing.  Make note that the curved end 
of the baffl e should be below the motor bolt boss.  
Tighten the thread cutting screw to 12-24 in-lbs.

Figure 2. – Mounting Low Fire Rate Baffl e in 
burner housing.
SK9698
Inspect/Prepare Installation Site
Figure 3. – Mounting Burner in Appliance
SK9668
Mount Burner on Appliance
  Verify that the air tube installed on the burner   pro-
vides the correct insertion depth. Refer to Figure 
3.
  The end of the air tube should normally be 1/4” 
back from the inside wall of the combustion cham-
ber. Never allow the leading edge of the retention 
ring to extend into the chamber, unless otherwise 
specifi ed by the appliance manufacturer.  
  Bolt the burner to the appliance using the factory-
welded fl ange.  
The burner is shipped without the by-pass plug in-
stalled.
Install the by-pass plug in two-pipe oil supply systems 
ONLY. 
Failure to comply could cause immediate pump 
seal failure, pressurized oil leakage and the po-
tential for a fi re and injury hazard. 
Do Not Install By-pass Plug 
with 1-Pipe System
WARNING
!
Connect Fuel Lines
The oil supply inlet pressure to the burner cannot 
exceed 3 psig
.  
Insure that a pressure limiting device is installed 
in accordance with the latest edition of NFPA 31. 
Do not install valves in return line.
Gravity Feed Systems: Always install an anit-
siphon valve in the oil supply line or a solenoid 
valve (RWB Part # 2182602U) in the pump/noz-
zle discharge tubing to provide backup oil fl ow 
cut-off protection. 

Damage to the fi lter or pump seals could cause 
oil leakage and a fi re hazard.
Oil Supply Pressure 
Control Required
!
!
CAUTION