Beckett CF 2500/ 3500 Manuel D’Utilisation

Page de 16
Instruction Manual 
– Model CF2500/CF3500 Oil Burner
5
Form 6104 BCF-35-R0699
3502
E
D
G
F
T
1
Table 2 – Air tube capacity vs. firebox pressure
Figure 2 – Air tube mounting dimensions
Insertion depth
Air tube to inside of chamber
– 0.25" ± 0.125"
Air tube length
Tube diameter
Figure 1 – Min. combustion chamber dimensions
Install the burner with a 2° pitch as shown.
❏  
Verify firing rate
• Refer to appliance manufacturer’s instructions (if avail-
able) for firing rate and nozzle selection. Otherwise, the
maximum recommended firing rate for the burner depends
on the length of the firing chamber and the distance from
the burner center to the chamber floor. Verify that the cham-
ber dimensions are at least as large as the minimum values
given in 
Figure 1
. If the appliance dimensions are smaller
than recommended, reduce the firing rate accordingly.
❏  
Verify air tube
• The information in this section may be disregarded if the
air tube is supplied by the appliance manufacturer.
• The following tube arrangements are available:
Model CF2500A
: Tube 
KP
— 17.0 to 19.9 GPH
Model CF2500
:
Tube 
KP
— 17.0 to 25.0 GPH
Model CF3500A
: Tube 
KM
— 17.0 to 35.0 GPH 
or
Tube 
KR
— 17.0 to 35.0 GPH
• Maximum firing capacity depends on the firebox pressure.
Use 
Table 2
 to verify the correct air tube type for the firing
rate required. (Tube 
KR
 [
CF3500A
] is an optional air tube
combination for maximum capacity rate. It requires a larger
I.D. flange No. 51631.)
• See 
Figure 2
 to verify the correct air tube length and air
tube combination code.
3501
A
L
Firing rate
 
Minimum dimensions
(all boilers)
A
L
17 gph
10.5"
48.0"
22 gph
11.5"
58.0"
27 gph
12.5"
66.0"
32 gph
12.5"
73.0"
35 gph
13.0"
77.0"
A.T.C. Codes
(A.T.C. = Air Tube Combination)
CF2500A/
CF2500
CF3500A
Tube KP
Tube KM
Tube KR
Dimensions
Dimensions
Dimensions
T
D
F
T
D
F
T
D
F
All — 6 ½"
3¼"
All —
8"
4 ½" All — 9 
¹⁵⁄₁₆
" 5 
¹⁄₈
"
6¾"
CF   66 KP
8"
CF   80 KM —
9 ¼"
CF   92 KM —
10¼" CF 102 KP
11 ½" CF  114 KM 11 ½" CF 114 KR
13¾" CF 136 KP
15"
CF  150 KM 14"
CF 140 KR
17¾" CF 176 KP
19"
CF  190 KM 19"
CF 190 KR
Firebox 
pressure
(In. W.C.)
Tube KP
Tube KM/KR
No 
reserve 
air
10% 
turndown
No 
reserve 
air
10% 
turndown
Maximum firing rate GPH
0.0
25.0
22.5
35.0
31.5
0.2
24.8
22.3
33.5
30.2
0.4
24.6
22.3
32.0
28.8
0.6
24.5
22.1
30.2
27.2
0.8
24.3
21.9
28.8
25.9
1.0
24.1
21.7
27.1
24.4
Note:  10% turndown indicates sufficient reserve air to reduce 
the CO
2
 in the flue to 90% of its value.
Note:  The above ratings may vary 5% due to variations in actual job 
conditions.