Professional Installer’s Responsibility:
Section: General Information
Follow these instructions 
exactly.
Failure to follow these instructions could 
lead to equipment malfunction and result 
in asphyxiation, explosion or fi re.
Please read all instructions before proceeding. 
Follow all instructions completely. 
This equipment must be installed, adjusted and 
started by a qualifi ed service agency that is licensed 
and experienced with all applicable codes and 
ordinances and responsible for the installation and 
commissioning of the equipment. 
The installation must comply with all local codes and 
ordinances having jurisdiction and the latest edition 
of the National Fuel Gas Code ANSI Z223.1 (NFPA 
54) and CAN1-B149.1 in Canada. 
y
y
y
Concealed damage – If you 
discover damage to the burner or 
controls during unpacking, notify the carrier at once and 
fi le the appropriate claim forms.
High altitude installations – Accepted industry practice 
requires no derate of burner capacity up to 2000 feet 
above sea level. For altitudes higher than 2000 feet, 
derate the burner capacity 2% for each 1000 feet above 
the 2000 feet.
50 Hz motors – The burner ratings, air settings and other 
adjustments are based on 60 hz motors at 3450 rpm.  
Derate fi ring capacity 20% when using 50 hz motors. 
Consult factory for specifi c application data.
Table 1 – Burner Specifi cations
Input fi ring range
300 to 1200 MBh
Fuel
Natural gas - 0.6 specifi c gravity typical
Gas train
Standard: UL listed/CSD-1 Confi guration
Options: IRI and FM
Manifold pressure 1.0 to 4.6 inches W.C. typical
Firing mode
On/Off or On/Off with Low Fire Start
Flame safeguard
RM7895A Standard (Options available)
Flame detection
Standard: Flame rod rectifi cation
Optional: Ultraviolet scanner
Air proving switch Standard
Gas pressure 
switches
Standard high and low
Ignition
Direct spark main fl ame
Motor
Standard: 1/3 HP; 3450 RPM; 120 
volt/60 hz, single phase
Optional motor: 50 or 60 hz (see notice 
for 50 hz), 240 volt single phase
Weight
55 lbs.
Dimensions
Refer to Figure 5.
Specifi cations
Special Requirements:
When contacting Beckett for 
service information — Please record the burner serial 
number (and have available when calling or writing). You 
will fi nd the serial number on the silver label located on 
the left rear of the burner. Refer to Figure 1.
Agency Approvals
Underwriters Laboritories
Certifi ed by C-UL
Accepted by N.Y.C.M.E.A.
Other approvals may be available 
and must be specifi ed at time of 
order.