Start-up checklist   –  Verify the following before at-
tempting to start burner.
Combustion air supply and venting have been inspected 
and verifi ed to be free of obstructions and installed in 
accordance with all applicable codes.
Oil nozzle has been selected correctly and securely 
installed in the nozzle adapter.
Fuel unit by-pass plug has not been installed for one-
pipe oil system.
By-pass plug has been installed for two-pipe oil 
system.
Fuel connection to nozzle line assembly is secure.
Dimension Z has been set per this instruction manual.
Fuel supply line is correctly installed, the oil tank is 
suffi ciently fi lled, and shut-off valves are open.
Burner is securely mounted in appliance, with pressure 
fi ring plate and gasket installed for pressurized chamber 
application.
Appliance has been fi lled with water (boilers) and 
controls have been operationally checked.
Burner has been installed in accordance with appliance 
manufacturer’s instructions (when available).
Also refer to appliance manufacturer’s instructions 
(when available) for start-up procedures.
Z dimension
Should be set per these instructions (see page 10). The 
top acorn nut (
Figure 12
, item 
d
) should never be loosened 
once the 
dimension is initially set.
Adjusting plate assembly 
(Figure 12)
 
Make sure spline nut (item 
b
) and bottom acorn nut (item 
c
) are loose before proceeding to next section.
Initial head position 
(Figure 12)
 
The indicator plate assembly (item 
e
) markings correspond 
to head position settings.
Slide the secondary adjusting plate (item 
f
) toward 
the rear of the burner until the number on the 
indicator plate corresponds to the initial head setting 
given in 
Tables 4a and 4b
 for the desired fi ring rate 
and burner (high-fi re).
Figure 12
 shows a typical example, with a head 
setting of 
6
.
When the head position has been set, tighten the 
bottom acorn nut (item 
c
) and the spline nut (item 
b
).
…
…
…
…
…
…
…
…
…
…
…
‰
‰
‰
y
y
y
Prepare the burner for start-up
Safety controls are designed and installed to provide 
protection.
Do not tamper with, or bypass any safety control. 
If a safety control is not functioning properly, 
shut off all main electrical power and fuel supply 
to the burner and call a qualifi ed service agency 
immediately.
y
y
y
Tampering with, or bypassing safety controls 
could lead to equipment malfunction and result  
in asphyxiation, explosion or fi re.  
Do Not Bypass Safety 
Controls
This burner must be installed and prepared for start-
up by a qualifi ed service technician who is trained 
and experienced in commercial oil burner system 
installation and operation.
Do not attempt to start the burner unless you are 
fully qualifi ed.
Do not continue with this procedure until all items 
in the “Prepare the burner for start-up” section have 
been verifi ed.  
Carefully follow the wiring diagrams, control 
instruction sheets, fl 
ame safeguard sequence 
of operation, test procedures and all appliance 
manufacturer’s directions that pertain to this 
installation.
If any of these items are not clear or are unavailable, 
call Beckett at 1-800-645-2876 for assistance.
y
y
y
y
y
Incorrect installation and mishandling of start-
up could lead to equipment malfunction and 
result in asphyxiation, explosion or fi re.
Professional Installation 
and Service Required
Keep Service Access 
Covers Securely Installed
These covers must be securely in place to prevent 
electrical shock, damage from external elements, 
and protect against injury from moving parts.  
All covers or service access plates must be in place 
at all times except during maintenance and service. 
This applies to all controls, panels, enclosures, 
switches, and guards or any component with a 
cover as part of its design.  
y