Beckett BRYAN STEAM CF1400 Manuel D’Utilisation

Page de 24
8
Form 6104 BCF23-R05
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or 
sprayed water.
Keep the installation clear of dust, dirt, corrosive 
vapors, and moisture.
Protective covers and more frequent maintenance 
may be required.
y
y
y
y
Wet, dusty environments could lead to blocked 
air passages, corrosion damage to components, 
impaired combustion performance and result in 
asphyxiation, explosion or fi re.
Protect Against Dust and 
Moisture 
 Stray light
‰
Dust and Moisture
‰
Mount the burner
Figure 4 – Mount fl ange(s) on air tube
Mount fl ange(s) on air tube
 
This section does not apply to burners with welded 
fl anges.
Do not install air tube on burner.
For non-pressure fi ring  fl ange, refer to Figure 4:  
Install gasket (item a) and fl ange (item c). Ignore the 
next paragraph.
For pressure-fi ring  fl ange, refer to Figure 4:  Slide 
gasket (item a) onto the air tube, making sure the top 
of the air tube is up. Predrill holes in the pressure fi ring 
plate (item b) to match the appliance studs. Slide the 
pressure fi ring plate (item b) and fl ange (item d) onto 
‰
y
y
y
the air tube as shown. Wrap ceramic fi ber rope (not 
shown) around the air tube and press tightly into the 
inside diameter of the fl ange (item c).
Slide the air tube (item d) into position in the 
appliance front. Tighten the fl ange-mounting-stud 
nuts. Set the insertion of the air tube so dimension G 
is 1/4” nominal.
Pitch the air tube at 2° from horizontal as shown and 
secure the fl ange to the air tube. 
y
y
Protect Against Stray 
Light Lockout 
Failure to follow these instructions could cause 
loss of burner operation resulting in no heat, an 
unplanned process interruption, work stoppage 
and the potential for frozen plumbing or other 
cold weather property damage.
The control must detect a dark, no-fl ame condition 
in order to start the burner or it will hold in the 
stray light lockout mode.
Shield the burner view window from direct expo-
sure to intense light. 
y
y
Protect the Air Tube 
From Overheating
Overheating could cause damage to the air tube 
and other combustion components leading  to 
equipment malfunction and impaired combustion 
performance.
The end of the air tube must not extend into the 
combustion chamber unprotected unless it has 
been factory-tested and specifi ed by the appliance 
manufacturer.
Position the end of the air tube 1/4” back from fl ush 
with the refractory inside entry wall to prevent 
damage from overheating.
y
y