Burnham Corporation
FDO
Series Boiler
Boiler
Burner
Chassis 
Spec.
  Air  Tube 
Combination
High 
Fire 
Rate
Nozzle
Head 
Setting
    Blue -    
Low Fire 
Air   or 
Shutter  
 Red - 
High Fire 
Air  or 
Band
Low Fire 
Pump 
Press.
High Fire 
Pump 
Press.
Pressure 
Firing 
Flange
Insertion
FDO-7
CF500  
BCF809 
CF60KK 
2.25
 2.00x45P      
1
3-1/2
0
N/A
140
51311
4.375"
FDO-9
CF500  
BCF809 
CF60KK 
2.75
 2.25x45P      
2
4
0
N/A
140
51311
4.375"
FDO-10
CF500  
BCF809 
CF60KK 
3.00
 2.75x45P      
2
4
0
N/A
140
51311
4.375"
FDO-12
CF800  
BCF403 
CF60KH 
4.00
 3.50x45P      
2
6
0
N/A
140
51311
4.375"
FDO-14
CF800  
BCF403 
CF60KH 
4.50
 4.00x45P      
2
7
0
N/A
140
51311
4.375"
FDO-15
CF800  
BCF403 
CF60KH 
5.00
 4.50x45P      
2
8
0
N/A
140
51311
4.375"
FDO-19
CF800  
BCF403 
CF60KJ 
6.00
 5.00x45P      
3
10
3
N/A
140
51628
4.375"
FDO-24
CF1400 
BCF205 
CF66KD 
7.50
 4.50x45P      
3
30
55
150
300
51629
4.375"
FDO-30
CF1400 
BCF205 
CF66KE 
9.00
 5.50x45P       1-1/2
45
75
150
300
51629
4.375"
FDO-38
CF2300A
BCF304 
CF66KG 
12.00
 7.00x45P      
1
25
45
150
300
51313
4.375"
FDO-45
CF2300A
BCF304 
CF66KG 
13.80
 8.00x45P       1-1/2
25
60
150
300
51313
4.375"
Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.     