Start-up checklist
Combustion air supply and venting have been inspected 
and verifi ed to be free of obstructions and installed in ac-
cordance with all applicable codes.
Oil nozzle has been selected correctly and securely in-
stalled in the nozzle adapter.
Fuel unit by-pass plug has not been installed for one-
pipe oil system.  
 
 
 
 
 
 
 
 
 
 
By-pass plug has been installed for two-pipe oil 
system.
Fuel connection to nozzle line assembly is secure.
Dimension Z has been set per this instruction manual.
Fuel supply line is correctly installed, the oil tank is suf-
fi ciently fi lled, and shut-off valves are open.
Burner is securely mounted in appliance, with pressure 
fi ring plate and gasket installed for pressurized chamber 
application.
Appliance has been fi lled with water (boilers) and controls 
have been operationally checked.
Burner has been installed in accordance with appliance 
manufacturer’s instructions (when available).
Also refer to appliance manufacturer’s instructions (when 
available) for start-up procedures.
Z dimension
  Should be set per the Set Z Dimension instructions 
detailed earlier in this manual. The acorn nut (Fig-
ure 6
, item c) should never be loosened once the Z 
dimension is initially set.
Initial head position (Figure 6)
The indicator plate assembly markings correspond to head 
position settings. 
Loosen the fastener (Figure 6, item d)  and slide the 
indicator plate until the number on the indicator plate 
corresponds to the initial head setting listed in Table 3, for 
the desired fi ring rate.
When the head position has been set, tighten the fastener 
and the spline nut.
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
y
y
y
Table 3 - Initial indicator adjustment plate  
 
        settings (head position)
Approximate adjust-
ing plate setting
Firing rate, gph
0
1.65
1
1.75
3
2.00
4
2.50
5
3.00
6
3.50
NOTE
These settings are approximate, 
and can vary depending on 
actual job conditions and overfi re 
pressure.
Firing rate, 
gph
Approximate head settings
Shutter
Band
1.65
  5
0
1.75
10
2
2.00
10
4
2.50
10
5
3.00
10
6
3.50
10
8
NOTE
These settings are approximate, and can 
vary depending on actual job conditions 
and overfi re pressure.
Table 4 - Initial air shutter and band settings
Initial air settings (Table 4)
Loosen the air band and shutter, and adjust to the 
 
 
approximate fi ring rate settings given in Table 4.
These initial settings should be adequate for starting the 
burner. Once the burner is in operation, the air settings 
will be adjusted for best performance as discussed later in 
this manual.
Follow the procedures described later in this manual for 
fi ne-tuning the air settings.
‰
y
y
y
Set appliance limit controls
Set the appliance limit controls in accordance with the 
appliance manufacturer’s recommendations.
Prepare the fuel unit for air venting
To vent air from one-pipe oil systems, attach a clear hose 
to the vent plug on the fuel unit. Provide a container to 
catch the oil. Loosen the vent plug.
Vent the air as described in the next section under Start 
the burner
.
‰
y
‰
y
y