Beckett CF2500 Manuel D’Utilisation

Page de 24
20
number  to reduce CO
2
 by 2 percentage points 
at a zero smoke level. (Increase O
2
 by 3 
percentage points at a zero smoke level.) 
 
 
 
 
 
 
Example: Reduce CO
2
 from 13.5% to 11.5%, 
with zero smoke (or increase O
2
 from 2.5% to 
5.5%).
A margin of reserve air has been added to 
accommodate variable conditions.
Check the breech draft pressure against the 
appliance manufacturer’s recommended setting 
(typically + 0.1” W.C.).
If the breech pressure is higher or lower than 
recommended level, adjust the appliance breech 
damper to achieve the specifi ed setting. Recheck 
the smoke and CO
2
 (or O
2
) levels. Adjust burner air 
if necessary.
Once all settings are complete and satisfactory, 
proceed to ‘Set Low-fi re Air’ Section.
Set Low-fi re Air
Move the low-fi re hold switch from the high fi re 
position 
to the low fi re hold position.
The damper will return to the low-fi re air 
setting.
Check the smoke and CO
2
 (O
2
) levels.
Pull a smoke sample from the fl ue.
The sample should be clean (zero smoke level).
Check the CO
2
 (O
2
) level:
CO
should be at 11 to 12% (O
2
 at 5.9 to 4.5%).
If the CO
2
 is less than 11% (O
2
 more than 
5.9%), decrease the air and check the smoke 
level.
Operate the burner from low fi re to high fi re and 
back to verify operation.
Turn the burner off. Wait one or two minutes (for 
chamber to clear) and then turn on again to verify 
starting characteristics.
Perform limit circuit performance test specifi ed 
by appliance manufacturer to verify operation of 
burner/appliance combination.
c.
7.
8.
9.
1.
a.
2.
a.
b.
c.
d.
e.
3.
4.
5.
If the burner motor does not start, reset the motor 
overload switch (if so equipped) and press the reset 
switch of the burner primary control.
Vent the fuel unit as soon as the burner motor starts 
rotating. To vent —
Attach a clear plastic tube to the air bleed valve 
(Figure 9 or 10 as applies, item p).
Place the end of the tube in a container to catch 
the oil. Then loosen the fuel unit air vent valve.
Tighten the air vent valve after all air has been 
purged.
IF burner stops during venting 
The burner primary control will lockout if 
fl ame is not established within its time limit.
This is typically 15 seconds for 7505 primary 
controls, but may be less for other fl ame 
supervisory controls.
The burner may lockout several times during 
the period needed to purge all the air. To 
extend air venting time, press the red reset 
button for 1/2 second during the prepurge 
cycle to continue purging with 7505 controls.
IF burner stops after fl ame established 
Additional venting is probably required. 
Repeat the air venting procedure.
Once fl ame is steady, proceed to the ‘Set High-fi re 
Air’
 Section air.
Set High-fi re Air
Allow the burner to run at low fi re until the 
appliance has warmed suffi ciently.
Visually check the fl ame. The fl ame should not be 
dark orange or smoky. If the fl ame appears to be 
smoking, increase the amount of air by readjusting 
the damper indicator to a higher number.
Once the appliance has warmed, the high-fi re 
setting can be checked and adjusted.
Locate the approximate air adjusting plate setting 
for high fi re in Table 4.
Place the low-fi re hold switch in the high-fi re 
position
. The damper motor will begin to rotate 
after four seconds.
Use combustion test instruments to adjust the 
burner.
Adjust the air by moving the red cam to a lower 
number until a trace of smoke is achieved with 
CO
2
 level as high as possible (lowest possible 
O
2
).
Example: 13.5% CO
2
 (2.5% O
2
) with a trace of 
smoke.
Increase the air by increasing the red cam 
6.
7.
-
-
-
8.
1.
2.
3.
4.
5.
6.
a.
b.
Section: Prepare the Burner for Start-up