CF2500/CF3500 Burner Manual
The fuel unit nozzle port pressure is factory set at 300 
psig. Some original equipment manufacturer burner 
applications may call for a lower pressure to obtain a 
required fi ring rate.  Do not change this pressure unless 
directed to do so by the appliance manufacturer.
Electrical Supply
Verify that the power connections available are correct 
for the burner. Refer to Figure 1.  All power must be 
supplied through fused disconnect switches.
Vent System
The fl ue gas venting system must be in good condition 
and must comply with all applicable codes.
Nozzle Pressure
Table 1 - Nozzle Capacities
Rated 
gph 
@ 100 
psig
Pressure - Pounds per square inch
125
150
175
200
250
300
5.00
5.59
6.13
6.61
7.07
7.50
8.66
5.50
6.15
6.74
7.27
7.78
8.70
9.54
6.00
6.71
7.33
7.94
8.48
9.49
10.40
6.50
7.26
7.96
8.60
9.20
10.30
11.25
7.00
7.82
8.56
9.25
9.90
11.06
12.12
7.50
8.38
9.19
9.91
10.60
11.85
13.00
8.00
8.94
9.80
10.58
11.31
12.65
13.85
8.50
9.50
10.45
11.27
12.06
13.40
14.70
9.00
10.06
11.02
11.91
12.73
14.20
15.60
9.50
10.60
11.70
12.60
13.50
15.00
16.45
10.00
11.18
12.25
13.23
14.14
15.81
17.32
10.50
11.74
12.85
13.90
14.85
16.60
18.18
11.00
12.30
13.47
14.56
15.55
17.39
19.05
12.00
13.42
14.70
15.87
16.97
18.97
20.78
12.50
13.98
15.31
16.54
17.68
19.76
21.65
13.00
14.54
15.92
17.20
18.38
20.55
22.52
13.50
15.10
16.53
17.85
19.09
21.34
23.38
Verify Burner Components
Burner nameplate (Figure 1), Model CF2500A/
CF2500/CF3500A
Air tube assembly
Mounting fl ange kit
Pedestal mounting assembly kit
 (recommended)
Oil nozzle, per Table 1 — Use only 45° to 70° 
solid pattern nozzles unless otherwise shown by 
appliance manufacturer or on the burner nameplate 
rating label.
The CF2500A, CF2500, and CF3500A are dual nozzle 
burners. To select the nozzles, use half of the maximum 
fi ring rate and select a nozzle under the 300 psig column. 
Select the corresponding nozzle from column 1 (Rated gph 
@ 100 psig
) two nozzles will be required.
Example: a 5.00 gph nozzle at 300 psig = 8.66 gph
 
Verify Firing Rate
Refer to appliance manufacturer’s instructions (if available) 
for fi ring rate and nozzle selection. Otherwise, the maximum 
recommended fi ring rate for the burner depends on the length 
of the fi ring chamber and the distance from the burner center 
to the chamber fl oor. Verify that the chamber dimensions are at 
least as large as the minimum values given in Figure 2. If the 
appliance dimensions are smaller than recommended, reduce 
the fi ring rate accordingly.



Correct Nozzle and Flow 
Rate Required
Incorrect nozzles and fl ow rates could 
result in impaired combustion, under-
fi ring, over-fi ring, sooting, puff-back of 
hot gases, smoke and potential fi re or 
asphyxiation hazards. 
Use only nozzles having the brand, fl ow rate (gph), spray 
angle and pattern specifi ed by the appliance manufacturer.
Follow the appliance manufacturer’s specifi cations for the 
required pump outlet pressure for the nozzle, since this 
affects the fl ow rate. 
Nozzle manufacturers calibrate nozzle fl ow rates at 
100 psig.
This burner utilizes pressures higher than 100 psig, 
so the actual nozzle fl ow rate will be greater than 
the gph stamped on the nozzle body.  
 
(Example: A 12.00 gph nozzle at 200 psig = 16.97 
gph and at 300 psig = 20.78 gph)
For typical nozzle fl ow rates at various pressures 
refer to Table 1.
y
y
y
Fire, Smoke & Asphyxiation 
Hazard
Carefully inspect the chimney or exhaust vent 
system.
Make sure it is properly sized and in good working 
condition. 
Follow the instructions supplied by the appliance 
manufacturer.
The installation must strictly comply with all 
applicable codes, authorities having jurisdiction and 
the latest revision of the National Fire Protection 
Association Standard  NFPA 31 for the installation of 
chimneys and vent sizing, (or CSA-B139 and CSA-
B140 in Canada).
Regulation by these authorities take precedence 
over the general instructions provided in this 
installation manual.