White Rodgers 1F82-261 White-Rodgers 80 Series Programmable Heat Pump Thermostat Manuel De Montage

Page de 8
TROUBLESHOOTING 
Reset Operation 
If a voltage spike or static discharge blanks out the display or
causes erratic thermostat operation, reset the thermostat by
pressing 
,
and TIME at the same time. If the thermostat
has power, has been reset and still does not function correctly
contact your heating/cooling service person or place of purchase. 
Symptom
Possible Cause
Corrective Action
No Heat/No Cool/No Fan
(common problems)
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel 
loose or not properly installed.
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety inter-
lock or door switch.
No Heat
1. System Switch not set to Heat.
2. Loose connection to thermostat or system.
3. Heating System requires service or thermo-
stat requires replacement.
Set System Switch to Heat and raise setpoint above room
temperature.
Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the setpoint
above room temperature. Within a five minutes the thermostat
should make a soft click sound. This sound usually indicates
the thermostat is operating properly. If the thermostat  does 
not click, try the reset operation listed above. If the thermostat
does not click after being reset, contact your heating and
cooling service person or place of purchase for a replace-
ment. If the thermostat clicks, contact the furnace manu-
facturer or a service person to verify the heating system is 
operating correctly.
No Cool
1. System Switch not set to Cool.
2. Loose connection to thermostat or system.
3. Cooling System requires service or thermo-
stat requires replacement.
Set System Switch to Cool and lower setpoint below room
temperature.
Verify thermostat and system wires are securely attached.
Same procedure as diagnostic for No Heat condition except
set the thermostat to Cool and lower the setpoint below the 
room temperature. There may be up to a five minute delay
before the thermostat clicks in Cooling if the compressor lock-
out option is selected in the configuration menu (Item 7).
Heat, Cool or Fan Runs Constantly.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in Heat/Cool/Fan system.
4. Fan Switch set to Fan On.
Check each wire connection to verify they are not shorted or
touching together. No bare wire should stick out from under
terminal screws. Try resetting the thermostat as described 
below. If the condition persists, the manufacturer of your
system or service person can instruct you on how to test 
the Heat/Cool system for correct operation. If the system 
operates correctly, replace the thermostat.
Furnace Cycles Too Fast or Too Slow 
(narrow or wide temperature swing)
1. The location of the thermostat and/or the size 
of the Heating System may be influencing the
cycle rate.
Item 2 in the Configuration Menu is the adjustment that
controls the cycle rate. If an acceptable cycle rate is not 
achieved using the FA (Fast) or SL (Slow) adjustment contact
a local service person for additional suggestions.
Cooling Cycles Too Fast or Too Slow 
(narrow or wide temperature swing)
1. The location of the thermostat and/or the size 
of the Cooling System may be influencing the
cycle rate.
The cycle rate for cooling is fixed and can not be adjusted.
Contact a local service person for suggestions.
Thermostat Setting and Thermometer 
Disagree
1. Thermostat thermometer setting requires
adjustment. 
The thermometer can be adjusted +/- 4 degrees as listed 
in item 8 of the Configuration Menu. No other adjustment is
possible.
Clock Loses or Gains Time
1. Loss of power to thermostat.
The thermostat will maintain its program in memory even with 
no power but the clock time will be incorrect when power is
restored. See No Heat/No Cool/No Fan (common problems)
above for items to check in the system.
Heat or Cool Starts Early
1.EMR activated
See Configuration Menu (Item 5).
Thermostat Does Not Follow 
Program
1. AM or PM set incorrectly in program.
2. AM or PM set incorrectly on the clock.
3. Voltage spike or static discharge.
Check current clock and program settings including the AM
or PM designations for each time period. If a voltage spike or
static discharge occurs use the Reset Operation listed above.
Blank Display and/or Keypad Not 
Responding
1. Voltage Spike or Static Discharge.
If a voltage spike or static discharge occurs use the Reset
Operation listed above.
www.white-rodgers.com
www. emersonclimate.com
White-Rodgers is a business 
of Emerson Electric Co.
The Emerson logo is a  
trademark and service mark 
of Emerson Electric Co.