White Rodgers 1311-103 Hydronic Zone Controls Catalogue
ZONE VALVES
HYDRONIC
CONTROLS
HYDRONIC ZONE CONTROLS
Two Types of Valves, 2-Wire or 3-Wire, for Zoning Hydronic
Systems up to 50 PSI
FEATURES
• Quiet operation.
• Valve stem made of stainless steel.
• Automatic recycling manual operator shows valve position at all times.
• Built-in auxiliary contacts to control burner or circulator relay.
• Motor can be removed from valve assembly without draining system.
SPECIFICATIONS
Electric rating of auxiliary switch. . . . . . . . 2.0A at 24VAC
Four zone valves operate with one 40 VA transformer
1311-102
PARTS AND ACCESSORIES
See end of this section for additional parts and accessories
• F19-0097 — Motor assembly for 3-wire zone valves
• F19-0104 — Motor assembly for 2-wire zone valves
• F84-0433 — Valve assembly for
3
/
4
”
(both series)
• F84-0434 — Valve assembly for 1” (both series)
• F84-0435 — Valve assembly for 1
1
/
4
”
(both series)
• F92-0227 — Water seal kits for
3
/
4
”
(both series)
• F92-0228 — Water seal kits for 1” (both series)
• F92-0229 — Water seal kits for 1
1
/
4
”
(both series)
DO NOT CHANGE VALVE ASSEMBLY WITHOUT DRAINING BOILER OR WHILE BOILER WATER IS
HOT. FAILURE TO RELIEVE WATER PRESSURE OR WAIT UNTIL WATER COOLS COULD RESULT IN
SCALDING INJURIES
VALVE
DIMENSIONS (inches)
SIZE
A
B
C
D
E
3
/
4
”
1
3
/
4
6
1
/
2
2
7
/
8
4
11
/
16
5
5
/
8
1”
1
15
/
16
6
3
/
4
3
1
/
8
4
13
/
16
5
7
/
8
1
1
/
4
”
2
1
/
8
7
1
/
8
3
11
/
16
5
6
1
/
4
CONTRACTOR TIP
: FOR HEAT / COOL APPLICATIONS, SEE 752-1 CONTROL ON PAGE 105.
TECHNICAL HELP
Zone Valve Troubleshooting. . . . . . . . . . . See pages 225-226
➀
Valve current is 0.4A only during opening or closing. For proper anticipation, select thermostat designed for use with a 3-wire zone valve.
➁
Valve current is 0.52A when opening but 0.2A when fully open: therefore set anticipator for 0.2A.
➂
GPM @ 1 PSI drop.
Maximum
Maximum Maximum
Flow
Friction Loss
Model
24VAC Thermostat
Time
Differential
Water
System Capacity
Equivalents
Number
Tubing Size (I.D.)
Circuit Rating
Cycle
Across Valve
Temp. Pressure
Cv
Ft. of Tubing
1361-102
3
/
4
”
0.2A ➁
Open: 45 seconds
15 PSI
240°F
50 PSI
23.5 ➂
2
1
/
2
Close: 60 seconds
(116°C)
1361-103
1”
0.2A ➁
Open: 45 seconds
15 PSI
240°F
50 PSI
37.0 ➂
3.5
Close: 60 seconds
(116°C)
1361-104
1
1
/
4
”
0.2A ➁
Open: 45 seconds
15 PSI
240°F
50 PSI
42.2 ➂
6.5
Close: 60 seconds
(116°C)
2-WIRE, 24V VALVES WITH SCREW TERMINAL WIRING PANEL AND AUXILIARY SWITCH
Maximum
Maximum Maximum
Flow
Friction Loss
Model
24VAC Thermostat
Time
Differential
Water
System Capacity
Equivalents
Number
Tubing Size (I.D.)
Circuit Rating
Cycle
Across Valve
Temp. Pressure
Cv
Ft. of Tubing
1311-102
3
/
4
”
0.4A ➀
Open: 45 seconds
15 PSI
240°F
50 PSI
23.5 ➂
2
1
/
2
Close: 45 seconds
(116°C)
1311-103
1”
0.4A ➀
Open: 45 seconds
15 PSI
240°F
50 PSI
37.0 ➂
3.5
Close: 45 seconds
(116°C)
1311-104
1
1
/
4
”
0.4A ➀
Open: 45 seconds
15 PSI
240°F
50 PSI
42.2 ➂
6.5
Close: 45 seconds
(116°C)
3-WIRE, 24V VALVES WITH SCREW TERMINAL WIRING PANEL AND AUXILIARY SWITCH
(SEE TABLE AT BOTTOM FOR COMPATIBLE THERMOSTATS)
1311 COMPATIBLE THERMOSTATS TABLE
Model
Number
Mechanical/
Digital
Display
Upgrade Model
Choices/Upgrade
Size
Mechanical
Digital
Display
1E56N-444
Mechanical
Analog
1F86ST-0471
Digital
Blue Single 4” Display
1F56N-444
Mechanical
Analog
1F95-0671
Digital
Blue Universal 6” Display
1F80-0471
Digital
Blue Single 4” Display
1F95-0680
Digital
Blue Commercial 6” Display
1F80ST-0471
Digital
Blue Selecto 4” Display
1F95-1277
Digital
Big Blue Universal 12” Touchscreen
1F83-0422
Digital
Blue Universal 4” Display
1F95-1280
Digital
Big Blue Commercial 12” Touchscreen
1F83-0471
Digital
Blue Universal 4” Display
1F95-1291
Digital
Big Blue Humidity 12” Touchscreen
1F85-0422
Digital
Blue Universal 4” Display
1F95EZ-0671
Digital
Blue Easy Reader 6” Display
1F85-0471
Digital
Blue Universal 4” Display
1F97-0671
Digital
Blue Single 6” Display
1F85ST-0422
Digital
Blue Selecto Universal 4” Display
1F97-1277
Digital
Big Blue Single 12” Touchscreen
1F86-0471
Digital
Blue Single 4” Display
1F97-1277
Digital
Big Blue Single 12” Touchscreen
?
PAGES
225-226
www.white-rodgers.com
103
103
HYDRONIC / APPLIANCE