Weil-McLain PLUS LINE PLUS-E017-A/1206 Manuel D’Utilisation

Page de 68
1
Part Number PLUS-E017-A/1206
PLUS LINE
 Indirect-Fired Water Heaters – Series 3
Domestic water 
piping
•  Union on domestic hot water outlet should be piped at a higher elevation than domestic
water drain valve. This will make draining water heater easier.
•  Install unions for easy removal of water heater. Use dielectric unions or couplings to protect
hot and cold water fittings from corrosion when connecting dissimilar materials such as
copper and galvanized iron pipe.
•  If copper pipe is used for domestic water connections, first solder pipe to a threaded adapter,
and then screw adapter into cold water inlet on top of water heater. Inlet contains an
internal plastic dip tube rated at 20°F, which can be damaged by heat from soldering.
•  When the supply pressure is higher than 0 psig, install a pressure reducing valve on cold
water supply line to prevent water loss through T&P relief valve.
•  If water heater will replace tankless coil in boiler,` disconnect piping to coil or remove coil
from boiler and replace with a cover plate. Allow water to drain from coil. Do not plug
tankless coil.
Plugging tankless coil inlet and outlet will result in severe personal injury,
death or substantial property damage.
Boiler water
•  Boiler water (including additives) must be practically non-toxic, having toxicity rating or
class of 1, as listed in Clinical Toxicology of Commercial Products.
•  If  antifreeze  is  used  in  boiler  system,  local  codes  may  require  a  backflow  preventer  on
cold water supply line. Use antifreeze specifically intended for hydronic heating systems.
Inhibited propylene glycol is recommended.
Do not use automotive, ethylene glycol or petroleum-based antifreeze. Do
not use any undiluted antifreeze. This can cause severe personal injury,
death or substantial property damage.
Water heater piping
  continued
A2