Utica Boilers UB95M-200 Guide De Référence

Page de 20
18
Para.
Name
Range
Boiler Display
Description
Gascom 
Software
Boiler
Display
Display Position
1st
2nd
3rd
4th
36
manual fans-
peed
-1 (auto op-
eration)
0 to 100 (%)
-1 (auto)
0 to 100 (%)
initial reading:
use this parameter, if desired, to manually 
set the boiler at a fixed input. The manual 
operation will only continue for 15 minutes. 
the  control  module  then  returns  to  auto-
matic operation.
P
.
3
6
after 2 to 3 seconds:
Blank
Blank
Setting
37 
(1st 
digit)
37 
(2nd 
digit)
PWm level  
CH-pump
1 to 4  
(pump speed) 
1 to 4
initial reading:
this function is not currently supported.
P
.
3
7
after 2 to 3 seconds:
Blank
Blank
digit 
1
digit 
2
38
t Hold
32
(feature off) 
32 to 176° F
32
(feature off)
 
32 to 176
initial reading:
Parameter 38 sets minimum standby tem-
perature for boiler. if boiler outlet or return 
water temperature is sensed at less than t 
Hold, the boiler fires (without pump operat-
ing to bring temperature up to t Hold).
P
.
3
7
after 2 to 3 seconds:
Blank
Blank
Setting
39
t6 top
2nd CH 
circuit
50 to 176° F
50 to 176
initial reading:
• This function is not currently supported.
• Sets max. target boiler temperature dur-
ing call for heat from 2nd CH circuit (same 
function as T1 Top for first CH circuit).
P
.
3
9
after 2 to 3 seconds:
Blank
Blank
Setting
40
t6 Foot
2nd CH 
circuit
50 to 70° F
50 to 70
initial reading:
• This function is not currently supported. 
• Sets min. target boiler temperature dur-
ing call for heat from 2nd CH circuit (same 
function as T1 Foot for first CH circuit).
P
.
4
0
after 2 to 3 seconds:
Blank
Blank
Setting
41
t6
differential
2nd CH 
circuit
2 to 54° F
2 to 54
initial reading:
• This function is not currently supported. 
• T6 Differential is the differential (hyster-
esis) for call for heat from 2nd CH circuit is 
master. Boiler starts when outlet tempera-
ture drops t6 differential below target out-
let temperature. 
P
.
4
1
after 2 to 3 seconds:
Blank
Blank
Setting
42 
(1st 
digit)
42 
(2nd 
digit)
Special pump 
CH/dHW 
Low/Off cycle
0, 1, 2, or 3 
(see right)
0
(feature off) 
1
(feature on)
0 to 3
0 or 1
initial reading:
First digit (Special pump CH/dHW):  
• 0 - NOT RECOMMENDED
 
normal circulator operation for CH and dHW 
 
• 1 - NOT RECOMMENDED 
Boiler circulator off on CH call for heat.  
normal circulator operation on dHW.  
• 2 - RECOMMENDED SETTING
 
Boiler circulator normal operation. dHW 
circulator 5-second delay before starting. 
• 3 - NOT RECOMMENDED 
Boiler circulator off on CH call for heat. 
dHW circulator 5-second delay before 
starting.
Second digit (Low/Off) cycle):
• If boiler continues firing at low fire for 3 
minutes  or  longer,  the  boiler  will  begin 
cycling  like  an  on/off  boiler,  firing  only 
at low fire, for cycle times of 10 minutes.  
• The boiler will return to normal (modulat-
ing)  operation  if  the  burner  is  either  off  or 
on for at least 9 minutes. 
P
.
4
2
after 2 to 3 seconds:
Blank
Blank
digit 
1
digit 
2
V - PARAMETER REFERENCE TABLE  continued