Utica Boilers UB95M-200 Guide De Référence
18
Para.
Name
Range
Boiler Display
Description
Gascom
Software
Boiler
Display
Display Position
1st
2nd
3rd
4th
36
manual fans-
peed
-1 (auto op-
eration)
0 to 100 (%)
-1 (auto)
0 to 100 (%)
initial reading:
use this parameter, if desired, to manually
set the boiler at a fixed input. The manual
operation will only continue for 15 minutes.
the control module then returns to auto-
matic operation.
operation will only continue for 15 minutes.
the control module then returns to auto-
matic operation.
P
.
3
6
after 2 to 3 seconds:
Blank
Blank
Setting
37
(1st
digit)
37
(2nd
digit)
PWm level
CH-pump
1 to 4
(pump speed)
1 to 4
initial reading:
this function is not currently supported.
P
.
3
7
after 2 to 3 seconds:
Blank
Blank
digit
1
digit
2
38
t Hold
32
(feature off)
32 to 176° F
32
(feature off)
32 to 176
initial reading:
Parameter 38 sets minimum standby tem-
perature for boiler. if boiler outlet or return
water temperature is sensed at less than t
perature for boiler. if boiler outlet or return
water temperature is sensed at less than t
Hold, the boiler fires (without pump operat-
ing to bring temperature up to t Hold).
ing to bring temperature up to t Hold).
P
.
3
7
after 2 to 3 seconds:
Blank
Blank
Setting
39
t6 top
2nd CH
circuit
50 to 176° F
50 to 176
initial reading:
• This function is not currently supported.
• Sets max. target boiler temperature dur-
ing call for heat from 2nd CH circuit (same
ing call for heat from 2nd CH circuit (same
function as T1 Top for first CH circuit).
P
.
3
9
after 2 to 3 seconds:
Blank
Blank
Setting
40
t6 Foot
2nd CH
circuit
50 to 70° F
50 to 70
initial reading:
• This function is not currently supported.
• Sets min. target boiler temperature dur-
ing call for heat from 2nd CH circuit (same
ing call for heat from 2nd CH circuit (same
function as T1 Foot for first CH circuit).
P
.
4
0
after 2 to 3 seconds:
Blank
Blank
Setting
41
t6
differential
2nd CH
circuit
2 to 54° F
2 to 54
initial reading:
• This function is not currently supported.
• T6 Differential is the differential (hyster-
esis) for call for heat from 2nd CH circuit is
master. Boiler starts when outlet tempera-
ture drops t6 differential below target out-
let temperature.
esis) for call for heat from 2nd CH circuit is
master. Boiler starts when outlet tempera-
ture drops t6 differential below target out-
let temperature.
P
.
4
1
after 2 to 3 seconds:
Blank
Blank
Setting
42
(1st
digit)
42
(2nd
digit)
Special pump
CH/dHW
Low/Off cycle
0, 1, 2, or 3
(see right)
0
(feature off)
1
(feature on)
0 to 3
0 or 1
initial reading:
First digit (Special pump CH/dHW):
• 0 - NOT RECOMMENDED
normal circulator operation for CH and dHW
• 1 - NOT RECOMMENDED
Boiler circulator off on CH call for heat.
normal circulator operation on dHW.
Boiler circulator off on CH call for heat.
normal circulator operation on dHW.
• 2 - RECOMMENDED SETTING
Boiler circulator normal operation. dHW
circulator 5-second delay before starting.
• 3 - NOT RECOMMENDED
Boiler circulator off on CH call for heat.
dHW circulator 5-second delay before
starting.
Second digit (Low/Off) cycle):
• If boiler continues firing at low fire for 3
minutes or longer, the boiler will begin
minutes or longer, the boiler will begin
cycling like an on/off boiler, firing only
at low fire, for cycle times of 10 minutes.
• The boiler will return to normal (modulat-
ing) operation if the burner is either off or
on for at least 9 minutes.
• The boiler will return to normal (modulat-
ing) operation if the burner is either off or
on for at least 9 minutes.
P
.
4
2
after 2 to 3 seconds:
Blank
Blank
digit
1
digit
2
V - PARAMETER REFERENCE TABLE continued