Precision Trading 60 R3.0 Manuel D’Utilisation

Page de 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 17 of 62 
3.5  DIGITAL PANEL METERS 
3.5.1.  VOLTMETER: 
3.5.1.1.  Accuracy (system): ±0.25% of reading, ±0.1V in the 200V scale, 
±0.01V in the 20V scale, ±0.005V in the 2V scale. 
3.5.1.2.  Input impedance: 1 M-OHM. 
3.5.1.3.  Scale 2V, 20V and 200V (1.999V, 19.9V and 199.9V) for external 
measurements and 20V and 200V for internal (battery) measurements. 
3.5.2.  AMMETER: 
3.5.2.1.  Accuracy (system): ±0.5% of reading, ±0.1A 
3.5.2.2.  Scale: 200A (199.9A) 
3.5.3.  SHUNT: 
3.5.3.1.  Accuracy: ±0.25% 
3.5.3.2.  Output: 1mV/A (100mV / 100A) 
 
3.6  FUSES and BREAKERS (Other than charge and discharge current limiters) 
3.6.1.  Mains: Dual Magnetic Circuit Breaker 
3.6.2.  Electronics and digital panel meters: 1/4A SLO BLO.