INSTALLATION 
 
10 
ME00070B 
TMS7 SERIES 
4.4  Ventilation
 
When installing TMS7 starters in an enclosure there must be 
sufficient air flow through the enclosure to limit heat rise within 
the enclosure. Temperature within the enclosure must be kept 
at, or below, the TMS7 maximum ambient temperature rating. 
 
If installing an TMS7 within a totally sealed enclosure a bypass 
contactor must be employed to eliminate heat dissipation from 
the soft starter during run. 
 
Soft starters dissipate approximately 4.5 watts per amp. The 
table below shows air flow requirements for selected motor 
currents. If other heat sources are installed in an enclosure 
along with the TMS7 an additional air flow allowance must be 
made for these items. Note that heat generation from 
semiconductor fuses, if used, can be eliminated by installing 
these within the bypass loop. 
 
Required Airflow  
m
3
/min 
m
3
/hour 
Motor 
Amps 
Heat 
(watts) 
5
o
Rise 
10
o
Rise 
5
o
Rise 
10
o
Rise 
10 
45 
0.5  0.2 
30 
15 
20 
90 
0.9  0.5 
54 
27 
30 
135 
1.4  0.7 
84 
42 
40 
180 
1.8  0.9 
108 
54 
50 
225 
2.3  1.1 
138 
69 
75 
338 
3.4  1.7 
204 
102 
100 
450 
4.5  2.3 
270 
135 
125 
563 
5.6  2.8 
336 
168 
150 
675 
6.8  3.4 
408 
204 
175 
788 
7.9  3.9 
474 
237 
200 
900 
9.0  4.5 
540 
270 
250 
1125  11.3  5.6 
678 
339 
300 
1350  13.5  6.8 
810 
405 
350 
1575  15.8  7.9 
948 
474 
400 
1800  18.0  9.0 
1080  540 
450 
2025  20.3  10.1  1218  609 
500 
2250  22.5  11.3  1350  675 
550 
2475  24.8  12.4  1488  744 
600 
2700  27.0  13.5  1620  810