Toshiba Remote Starter ME00070B Manuel D’Utilisation

Page de 32
PROGRAMMING 
 
18 
ME00070B 
TMS7 SERIES 
7.2 
Function List 
 
No. 
Function 
 
Primary Motor Settings 
Default 
Setting
 
Motor full load current 
Current limit 
350 
Minimum current 
350 
Start ramp time 
Stop ramp time 
Motor trip class 
10 
Current imbalance sensitivity  
Undercurrent protection 
20 
Stall protection 
400 
 
Start/Stop Formats 
 
10  Soft stop mode 
 
Starter Functionality 
 
20  Local/Remote operation 
21  Relay output A functionality  
11 
22  Relay output B functionality  
10 
23  Relay output C functionality  
 
Protection Settings 
 
30  Phase rotation 
31  Restart delay  
15 
32  Current imbalance 
 
Set Points 
 
40  Low current alarm 
50 
41  High current alarm 
105 
42  Motor temperature alarm 
80 
43  Field calibration 
100 
 
Analogue Output (Motor Current - % FLC) 
 
50  4-20mA output range - max 
100 
51  4-20mA output range - min 
 
Serial Communications 
 
60  RS485 timeout 
61  RS485 baud rate 
62  RS485 satellite address 
20 
 
Auto Reset 
 
70  Auto-reset - configuration 
71  Auto-reset - number of resets 
72  Auto-reset - group A & B delay  
73  Auto-reset - group C delay  
 
Secondary Motor Settings 
 
80  Motor full load current 
81  Current limit 
350 
82  Minimum current 
350 
83  Start ramp time 
84  Stop ramp time 
85  Motor trip class 
10 
86  Current imbalance sensitivity  
87  Undercurrent protection 
20 
88  Stall protection 
400 
 
Protection Delays 
 
90  Current imbalance trip delay 
 
Read Only Data 
 
100  Model Number 
101  Fault History 
 
Restricted Functions 
 
110  Access code 
111  Update access code 
112  Function lock 
113  Restore function settings 
 
 
 
 
7.3 
Function Descriptions 
 
1. 
Motor Full Load Current 
Range: Model Dependant (Amps) 
Default Setting: Model Dependant (Amps) 
Description: Sets the TMS7 for the connected motor’s full load 
current. 
Adjustment: Set to the Full Load Current (amps) rating shown 
on the motor nameplate. 
 
2. 
Current Limit 
Range: 100 – 550 % FLC 
Default Setting: 350% FLC 
Description: Sets the current limit for the Constant Current start 
mode. 
700%
500%
300%
100%
50%
100%
ROTOR SPEED
( % Full Speed)
eg. Function 2. Current  Limit = 350% x FLC
 
Adjustment: The required setting for the Current Limit function 
is installation dependant and should be set such that: 
• 
The motor is supplied with sufficient start current to enable 
it to produce torque adequate to easily accelerate the 
connected load. 
• 
Desired starting performance is obtained. 
• 
TMS7 ratings are not exceeded. 
 
3. 
Minimum Current 
Range: 100 – 550 % FLC 
Default Setting: 350% FLC 
Description: Sets the minimum current level for the Ramp Start 
mode. 
700%
500%
300%
100%
50%
100%
ROTOR SPEED
(% Full Speed)
Function. 2 Current Limit = 350% x FLC
Function. 3 Minimum Current = 200% x FLC
Function. 4 Start Ramp Time = 10 secs