Toshiba Remote Starter ME00070B Manuel D’Utilisation

Page de 32
APPLICATION EXAMPLES 
 
28 
ME00070B 
TMS7 SERIES 
 
8.4  Two Speed Motors 
I34
I33
LEGEND
K2A
K1M
REMO TE  START  RELAY  (HIGH  SPEED)
LINE  CONTACTOR  (HIGH SPEED)
K1A
REMOTE  START  RELAY  (LOW SPEED)
K2M
K3M
S1
LINE  CONTACT OR  (LO W  SPEED)
STAR  CONTACT OR  (HIGH SPEED)
RESET  PUSHBUTT ON
NOTES
CONTACTORS K2M AND  K3M MUST BE
MECHANICALLY  INTERLOCKED.
1.
K1A
K2A
K1A
K2A
REMOTE LOW SPEED
START  INPUT
REMOTE HIGH  SPEED
START  INPUT
K3M
K1A
K2M
K2A
OUT PUT C
R11
R14
R12
A3
THERM.
A1
A2
SUPPLY
MOT OR
THERMISTOR
K1M
C2
C1
T1
T2
T3
E
L1
L2
L3
L1B
L3B
L2B
3  PHASE
SUPPLY
K3M
K2M
T4
T5
T6
T 1
T2
T3
TO  DUAL  SPEED  MOTOR
DAHLANDER T YPE
SEE  NOT E1.
K1M
K3M
K2M
K3M
K1M
CONTROL  SUPPLY
CONTROL
SUPPLY
FLC SELECT
K1A
I44
I43
START
K1M
RESET
STO P
K2M
S1
I22
I21
I12
I11
 
Description: 
The TMS7 can be configured for control of dual speed Dahlander type motors. In this application the TMS7 is employed with a High Speed 
contactor (K1M), Low Speed contactor (K2M) and a Star contactor (K3M). 
On receipt of a High Speed start signal the High Speed contactor (K1M) and Star contactor (K3M) are closed. The TMS7 then controls the 
motor according to the Primary Motor Parameter set. (Function Numbers 1~9) 
On receipt of a Low Speed start signal the Low Speed contactor (K2M) is closed. The relay contact across Input A is also closed causing 
the TMS7 to control the motor according to the Secondary Parameter set (Function Numbers 80~88). 
 
Function Settings: 
Function 23. Relay Output C Functionality = 0 (Assigns the Trip function to Relay Output C)