8.2.   Monitoring from the computer
This section explains how to monitor the operating status of the inverter from the computer.
„
 
Monitoring of the operation frequency from the computer (FE00, FD00)
Operation frequency (frequency immediately before the occurrence of a trip):
Communication Number FE00 (Minimum unit: 0.01 Hz)
Operation frequency (current frequency): Communication Number FD00 (Minimum unit: 0.01 Hz)
Ex.: Monitoring of operation frequency (during 50 Hz operation) ... (1388H = 5000d, 5000 x 0.1 = 50
Hz)
Computer 
→ Inverter
Inverter 
→ Computer
(RFD00) 
CR
(RFD001388) 
CR
„
 
Inverter operating status (FE01, FD01)
Operating status (status immediately before the occurrence of a trip):
Communication Number FE01
Operating status (current status):
Communication Number FD01
Table 2 Data construction of inverter operating status (FE00/FD00) (*: FD01 supports the VF-S11 and later models.)
Bit Specifications
0
1
S7 S9
S11/nC1
Remarks
0 Failure FL
No output
Output in prog-
ress
- -
9
1 Failure
Not tripped
Tripped
- -
9
Trip statuses include 
and trip retention status.
2 Alarm
No alarm
Alarm issued
- -
9
3 Reserved
-
-
- -
-
4 Motor section (1 or 2)
(THR 2 selection)
Motor 1 (THR 1) Motor 2 (THR 2)
- 9
9
THR1: PT=set value, vL, vb, Thr
THR2:PT=0, F170, F172, F173
5 PI control OFF
PI control
permitted
PI control
prohibited
- 9
9
6 Acceleration/deceleration
pattern selection (1 or 2)
Acceleration/
deceleration
pattern 1 (AD 1)
Acceleration/
deceleration
pattern 2 (AD 2)
9 9
9
AD1 :ACC, DEC,
AD2 :F500, F501
7 DC braking
OFF
Forced DC
braking
9 9
9
8 Jog run
OFF
Jog run
9 9
9
9 Forward/reverse run
Forward run
Reverse run
9 9
9
10 Run/stop
Stop
Run
9 9
9
11 Coast stop (ST=OFF)
ST=ON
ST=OFF
- 9
9
12 Emergency stop
Not emergency
stop status
Emergency stop
status
- 9
9
13 Standby ST=ON
Start-up process
Standby
- -
9
Standby: Initialization completed,
not failure stop status, not alarm
stop status (MOFF, LL forced
stop or forced stop due to a
momentary power failure),
ST=ON, and RUN=ON
14 Standby
Start-up process
Standby
- -
9
Standby: Initialization completed,
not failure stop status, and not
alarm stop status (MOFF, LL
forced stop or forced stop due to
a momentary power failure)
15 Reserved
-
-
- -
-