BEFORE INSTALLING
This  information  is  included  as  a  quick  reference  installation 
guide. Refer to the appropriate control panel installation manual 
for detailed system information. If the modules will be installed 
in an existing operational system, inform the operator and local 
authority that the system will be temporarily out of service.
NOTICE:  This  manual  should  be  left  with  the  owner/user  of 
this equipment.
GENERAL DESCRIPTION
Relay Module, Model EM-1RI, is to be designed for use in activa-
tion of the types of products that are generally connected to an in-
telligent fire alarm system. It provides two sets of form C contacts 
that switch together (one DPDT relay). There is also an input that 
is capable of monitoring a dry set of contacts for open or closed 
conditions. The module also has on-board short circuit isolators 
to prevent shorts on the signaling line circuit from disabling more 
than one device on the intelligent loop.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a 
listed compatible control panel.
D500-61-00 
I56-2023-004
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
EM-1RI Relay Module
SPECIFICATIONS
Normal Operating Voltage: 
15 to 30 VDC
Standby Current: 
500 µA max. average (continuous broadcasts)
Alarm Current: 
2.0 mA (red LED on)
Short Circuit Current
 
Dry Control Input: 
30 µA max. Avg. (5VDC)
Maximum Resistance
 
Dry Contact Input: 
100 Ω
Temperature Range: 
32°F to 120°F (0°C to 49°C)
Humidity: 
10 to 93% RH Non-condensing
Dimensions: 
4.17˝ H x 4.26˝ W x 1.22˝ D
 
(106 mm H x 108 mm W x 31 mm D)
Accessories: 
Wall cover plate (included)
 
SMB500 Surface Mount Electrical Box
 
CB500 Control Module Barrier
LED
INDICATOR
IR 
RECEIVER
C0166-00
MOUNTING
The module mounts directly to 4˝ square electrical boxes. The box 
must have a minimum depth of 2
1
8
˝. Modules must be mounted 
with the arrow facing upward for proper operation of the IR pro-
gramming  tool.  Surface  mounted  electrical  boxes  (SMB500)  are 
available from System Sensor.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.
I56-2023-004
CURRENT RATING
MAXIMUM VOLTAGE
LOAD DESCRIPTION
APPLICATION
3 A
30 VDC
Resistive
Non-Coded
2 A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-Coded
.9 A
125 VDC
Resistive
Non-Coded
.5 A
30 VDC
Inductive (L/R=5ms)
Coded
1 A
30 VDC
Inductive (L/R=2ms)
Coded
.3 A
125 VAC
Inductive (PF=.35)
Non-Coded
1.5 A
25 VAC
Inductive (PF = .35)
Non-Coded
.7 A
70.7 VAC
Inductive (PF=.35)
Non-Coded
2 A
25 VAC
Inductive (PF=.35)
Non-Coded