Hardware operation 
3.2 Operating the inverter 
14 
3.2.2 Operating 
mode 
You can choose between modes "Automatic" and "Test". 
In Test mode, you can adjust the DC voltage manually. In Automatic mode, the inverter determines the 
Maximum Power Point (MPP) automatically. It also displays currently active fault messages.  
To select Test mode, turn the keyswitch to the "TEST" position. To select Automatic mode, turn the 
keyswitch to the "AUTO" position. 
3.2.3  Switching the inverter on and off 
The inverter switches on and off automatically in AUTO mode. Manual switching on and off is possible in 
both TEST mode and AUTO mode. 
The control electronics and control panel of the inverter are switched off temporarily in order to save 
energy. When the inverter is in this state, it cannot be operated via the panel. However, you can switch 
on the control electronics and control panel for maintenance and commissioning purposes. To do so, 
open the cabinet door and press the Fast ON button inside the inverter. Once you have switched on the 
panel, you can switch the inverter on and off as described below. 
To switch off the inverter during operation, briefly press the OFF button on the operator panel (less than 3 
seconds). 
To switch on the inverter, briefly press the OFF button on the operator panel (less than 3 seconds) in 
TEST mode. 
 
3.2.4  Local/Remote selector switch 
If the selector switch is set to Local, errors can only be acknowledged locally and the inverter can be 
started manually. Remote access is blocked in this switch position. 
In the Remote position, errors can also be acknowledged and the inverter started by a plant monitoring 
system (such as WinCC). In this position, the inverter can also be operated locally and started manually. 
 
 
Figure 3-3 Fast ON button and local/remote selector switch