Siemens Advanced Motor Master System for Medium Voltage Motors SAMMS-MV Manuel D’Utilisation
44
Appendix A Technical Specifications
FLC
FLC
FLC
FLC
FLC
FLC
FLC
FLC
FLC
O
O v
v e
e rrllo
o a
a d
d S
S p
p e
e c
c iiffiic
c a
a ttiio
o n
n s
s
Overload classes
Overload classes 2 through 23 with one second increments.
Trip Characteristics
Tripping time at 6 x I = 95% of the overload class (±5%).
Tripping time at 1.5 x I within two minutes for warm conditions for all classes.
Tripping time at 1.5 x I within two minutes for warm conditions for all classes.
Tripping threshold
(1.1 ± 0.05) x I for motors with 1.00 service factor, and
(1.2 ± 0.05) x I for motors with 1.15 service factor.
(1.2 ± 0.05) x I for motors with 1.15 service factor.
Tripping time
20 minutes @1.15 x I for motors with service factor 1.
Mechanical jam protection
SAMMS-MVX only
SAMMS-MVX only
Sudden increase of the motor running current. Pick-up current adjustable from 120 to
400% in increments of 5% of I . Pick-up time 360 msec.
Default values: 200% I .
400% in increments of 5% of I . Pick-up time 360 msec.
Default values: 200% I .
Loss of load protection
SAMMS-MVX only
SAMMS-MVX only
Sudden decrease of motor running current. Pick-up current adjustable form 20 to 95% in
increments of 5% of I . Pick-up time 360 msec.
Default values: 50% I .
increments of 5% of I . Pick-up time 360 msec.
Default values: 50% I .
Process current warning
SAMMS-MVX only
SAMMS-MVX only
Settings from 0 to 100% of I .
Accuracy
± 5% of overload trip curve values.
± 2% repeat accuracy.
± 2% repeat accuracy.
Phase unbalance protection
Response time after 1 second
Shifted trip threshold value to 0.9 x I at 40% phase unbalance.
Shifted trip threshold value to 0.9 x I at 40% phase unbalance.
Equipment ground fault protection
Response time after 1.4 seconds.
Pick-up time: 360 msec.
Pick-up time: 360 msec.
Pick-up current:
Overload Relay Size Pick-up Current Default
H3A 7A- I 10A
H3B 7A- I 10A
H3C 7A- I 10A
H6 7A- I 20A
Overload Relay Size Pick-up Current Default
H3A 7A- I 10A
H3B 7A- I 10A
H3C 7A- I 10A
H6 7A- I 20A
Rotor protection
Cold stall time adjustable from 5 to 100 seconds in increments of 1 second. If cold stall
time is not known, default value shall be according to the type of motor used.
Motor Type Cold Stall Time
Open Drip Proof (ODP) 10 Seconds
Totally Enclosed Fan Cooled (EFC) 20 Seconds
time is not known, default value shall be according to the type of motor used.
Motor Type Cold Stall Time
Open Drip Proof (ODP) 10 Seconds
Totally Enclosed Fan Cooled (EFC) 20 Seconds
Ambient temperature
Motor ambient temperature adjustable 0 - 70°C in increments of 5°C.
Default value: 40°C.
Default value: 40°C.