Commissioning 
 
9.2 Procedure 
1. Disconnect the parallel connection 
Only connect motor 1 to the power module. 
2. Commission motor 1 as a single motor: 
●  Observe the information provided in the section titled "Commissioning checks performed 
in a current-free state". 
●  Perform commissioning up to and including Point 8 as per the section titled 
"Commissioning a single torque motor (SINUMERIK example)". 
3. Traverse the axis and check that it is functioning correctly 
4. Note the commutation angle offset of motor 1 
MD 1016 (motor 1) = _ _ _ _ _ _ _ _ electrical degrees 
5. Switch off and wait until the DC link has been discharged 
6. Instead of motor 1, connect motor 2 to the power module 
 
NOTICE 
 
For a Janus configuration, interchange phases U and V (see PHB 1FW6, chapter titled 
"Power connection for parallel operation"). 
 
7. Switch on with the pulse and controller enables deactivated 
8. Determine the commutation angle offset of motor 2 
●  For an incremental measuring system or 
●  For an absolute measuring system; switch drive off (NCK reset) 
9. Rotate the axis and check that it is functioning correctly 
Does the axis rotate with a positive speed setpoint in the required direction? 
●  No → Change MD 32100 (direction of rotation) 
Is the angle of rotation OK (specification = 10°→ angle = 10°)? 
10. Note the commutation angle offset of motor 2 
MD 1016 (motor 2) = _ _ _ _ _ _ _ _ electrical degrees 
1FW6 Built-in torque motors 
Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7 
183