1.2 AS System File for PROGRAF AS+ 
Your commisioning diskette contains a directory PROGRAF after extracting. This contains 
the system file AS.SYS required for PROGRAF AS+. 
Copy the file AS.SYS into your PROGRAF PC into the directory 
 drv:\PROGRAF\USER\ 
The system file of the AS 488/TM automation system is then known to PROGRAF AS+. 
Carry out your PROGRAF AS configuring in the usual manner. 
 
Note: 
From PROGRAF AS+ V3.00 onwards, the AS commands FORM, LA, AR, DI and DEL are 
also allowed for online structuring. 
After "LA,name;" PROGRAF AS+ terminates the coupling to AS 488/TM (message "BUS 
STRUCTURING ABORTED"). The coupling must be re-established after the loading and 
reset procedure is complete (new ANMS). 
Caution: 
Under no circumstances should PROGRAF AS+ be stopped while the AS is 
 
being reset, as this causes the bus structuring in the AS to remain active. 
 
If it should happen nonetheless, the user of PROGRAF AS+ should logon on 
 the 
same 
AS. 
 
 
 
1.3 Master Type File for COM ET200 / COM PROFIBUS 
In the DOKU folder on the IBS tool diskette, there are two files for the ET200 configuration 
tool COM ET200 or COM PROFIBUS. 
The master type-file ‘SI8050AX.2MH’ must be copied to the MASTERS directory of the 
installed COM PROFIBUS. Its contents specify the AS 488/TM as the host system and the 
module card IF964 as the DP master. The bitmap file ‘AS488TM.BMP’ must be copied into 
the BITMAPS directory. Once COM PROFIBUS is started, the ‘Read in type files’ menu 
item or the ‘Read in GSD files’ menu item from within the ‘file’ menu need be activated 
only once (see also DP_PRO_D.doc). 
Note: 
In the case of COM PROFIBUS, these files are already supplied from V3.1 
 onwards.