Sanyo ECOi Manuel D’Utilisation

Page de 32
11
SANYO’s Mini ECOi is suited  
for numerous commercial and 
premium residential applications.
SANY
O
 
OUTDOOR
CHX
SERIES
Mini ECOi Multi Split VRF Heat Pump
CHX (R) 
03652 
/
 
CHX (R) 
05252
 
KEy FEaturES:
 
Single Phase 208/230 volts
*
 One Outdoor Unit Connects As Many As 9 Indoor Units
  (50%-130% ratio of indoor to outdoor capacity)
*
 Inverter Driven Twin Rotary Compressor
*
 Operating Range (Outdoor Ambient)
 
- Cooling 14 FDB to 113 FDB
 
- Heating -4 FWB to 59 FWB
*
 Ultra Quiet Operation As Low As 51dB(a)
*
 Variable Speed DC Fan Motor
*
 Piping:
 
-656 Feet - Maximum Total Liquid Line 
 
-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor)
 
-131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)
*
 Defrost control, Reverse cycle, microprocessor control
*
 External finish: galvanized steel plate with powder paint
Refrigerant control: Electronic expansion valve
DESCrIPtION
CHX (R)
 
03652
 
CHX (R)
 
05252
 
POwEr SOurCE 208-230V/1PH/60Hz
208-230V/1PH/60Hz
PErFOrMaNCE
COOLINg CAPACITY   
SEER
HEATINg CAPACITY
 HSPF
AIR CIRCULATION (HI)    
Ducted      Non-Ducted      Mix
40,000       39,000              39,000   BTU/H
14.20         16.40                15.30
40,500       42,500              41,500   BTU/H
8.20             9.60                    8.90
3,530 CFM
Ducted       Non-Ducted       Mix
51,500        52,000               51,500  BTU/H
14.6            17.3                   16
57,500        58,000               58,500  BTU/H
7.7                9.5                     8.6
3,530 CFM
ELECtrICaL ratINGS
VOLTAgE RATINg 
 AVAILABLE VOLTAgE RANgE
RUNNINg AMPERES
MAX. RUNNINg AMPERES
 POWER INPUT
MAX. POWER INPUT
MIN. CIRCUIT AMPACITY
MAX CIRCUIT AMPACITY
COOLINg                 HEATINg
208 / 230 V              208 / 230 V
187—253 V            187—253 V
14.6 / 13.6 A           14.6 / 13.6 A
23.6 / 23.6 A           23.6 / 23.6 A
2.76 / 2.76 Kw       2.88 / 2.88 Kw
4.85 / 4.85 Kw        4.85 / 4.85 Kw
18  A
30  A
COOLINg                 HEATINg
208 / 230 V              208 / 230 V
187—253 V            187—253 V
23.5 / 21.9 A           23.5 / 21.9 A 
28 / 28 A                 28 / 28 A
4.57 / 4.57 Kw        4.58 / 4.58 Kw
5.72 / 5.72 Kw        5.7 2 / 5.72 Kw 
29  A
50  A
rEFrIGEraNt tuBING
LIMIT OF TUBINg LENgTH
LIMIT OF ELEVATION DIFFERENCE
BETWEEN THE 2 UNITS
 
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
656 ft
Outdoor unit is higher than indoor unit: 164
Outdoor unit is lower than indoor unit: 131
rEFrIGEraNt tuBE DIaMEtEr
LIQUID TUBE IN.
gAS TUBE IN.
3/8"
5/8"
3/8"
3/4"
uNIt DIMENSIONS
INCHES (") / LBS.
SHIPPINg WEIgH /  VOLUME
EXTERNAL AIR TEMP. OPERATION RANgE
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
Height/ Width/ Depth/ Net Weight
49”/ 37”/ 14”/ 229 lbs.
247 lbs. / 19.8 ft.
3
Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)
 *
 
NOtE
:
 
*(r) in Model # indicates Salt Protection - Special Order