Schneider Electric DuraDrive Direct Coupled Actuators MA4X-707X Manuel D’Utilisation

Page de 24
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
13
B
Shaft Rotates 
Clockwise
To Open
Shaft Rotates
Counterclockwise
To Open
A - Left
A - Right
This step determines
shaft rotation. Linkage 
may change damper direction.
For MA41-707X and MA41-715X only (manual override). 
For MA40-707X and MA40-715X, proceed to step C.
R
R
L
LO
CK
R
L
LOCK
If position indicator does not point to zero:Unlock the actuator.
Insert hex wrench into manual override.
Crank the actuator so the indicator points to 
.
Lock the actuator.
Caution:   Do not crank the manual
  override if power is applied
  to the actuator.
Manual Override
Unlock
Long Shaft
Short Shaft
Min. 3 1/2" (90 mm)
3/8" to 3/4" Diameter (10 mm to 20 mm)
3/8" to 1/2" Square (10 mm to 13 mm)
Min. 3/4" (20 mm)
Move the damper to its normal position. Verify the controller action is set to match the 
damper application.
Normally closed damper: when damper is closed, actuator position indicator should 
be at 0°. When damper is open, actuator position indicator should be at 90°.
Normally opened damper: when damper is open, actuator position indicator should 
be at 0°. When damper is closed actuator position indicator should be at 90°.
Fully engage hex wrench
into manual override before 
winding.