RuggedCom Server RS910W Manuel D’Utilisation

Page de 31
18 
 
2007 RuggedCom Inc. All rights reserved 
 
Rev100
 
4  Ethernet Ports 
4.1  RJ45 Ethernet Ports 
 
The RS910W has several 10/100Base-TX ports that allow connection to standard category 5 
(CAT-5) unshielded twisted-pair (UTP) cable with RJ45 male connectors. The RJ45 receptacles 
are directly connected to the chassis ground on the unit and can accept CAT-5 shielded twisted-
pair (STP) cables. If shielded cables are used, care must be taken to ensure the shielded cables 
do not form a ground loop via the shield wire and the RJ45 receptacles at either end. The figure 
below shows the RJ45 port pin-out. 
 
 
Figure 13 - RJ45 Ethernet port pin-out 
 
Pin 
Signal 
+Rx 
-Rx 
+Tx 
No Connection 
No Connection 
-Tx 
No Connection 
No Connection 
Case 
Shield (Chassis Ground) 
Table 2 - RJ45 Ethernet port pin-out 
 
NOTE: RuggedCom does not recommend the use of CAT-5 (10/100Base-TX communications) 
cabling of any length for critical real-time substation automation applications. However, transient 
suppression circuitry is present on all copper ports to protect against damage from electrical 
transients and to ensure IEC 61850-3 and IEEE 1613 Class 1 conformance. This means that 
during the transient event communications errors or interruptions may occur but recovery is 
automatic.