Combustible Wall Chimney Connector Pass-Throughs. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Method A. 12” (304.8 mm) Clearance to Combustible Wall 
Member: Using a minimum thickness 3.5” (89 mm) brick and 
a 5/8” (15.9 mm) minimum wall thickness clay liner, construct 
a wall pass-through.  The clay liner must conform to ASTM 
C315 (Standard Specification for Clay Fire Linings) or its 
equivalent. Keep a minimum of 12” (304.8 mm) of brick 
masonry between the clay liner and wall combustibles.  The 
clay liner shall run from the brick masonry outer surface to 
the inner surface of the chimney flue liner but not past the 
inner surface.  Firmly grout or cement the clay liner in place 
to the chimney flue liner.   
Method B. 9” (228.6 mm) Clearance to Combustible Wall 
Member: Using a 6” (152.4 mm) inside diameter, listed factory-
built Solid-Pak chimney section with insulation of 1” (25.4 mm) 
or more, build a wall pass-through with a minimum 9” (228.6 
mm) air space between the outer wall of the chimney length 
and wall combustibles.  Use sheet metal supports fastened 
securely to wall surfaces on all sides, to maintain the 9” (228.6 
mm) air space.  When fastening supports to chimney length, 
do not penetrate the chimney liner (the inside wall of the Solid-
Pak chimney).  The inner end of the Solid-Pak chimney 
section shall be flush with the inside of the masonry chimney 
flue, and sealed with a non-water soluble refractory cement. 
Use this cement to also seal to the brick masonry penetration.
 
Method C. 6” (152.4 mm) Clearance to Combustible Wall 
Member: Starting with a minimum 24 gage (.024” [.61 mm]) 
6” (152.4 mm) metal chimney connector, and a minimum 24 
gage ventilated wall thimble which has two air channels of 1” 
(25.4 mm) each, construct a wall pass-through. There shall 
be a minimum 6” (152.4) mm separation area containing 
fiberglass insulation, from the outer surface of the wall 
thimble to wall combustibles.  Support the wall thimble, and 
cover its opening with a 24-gage minimum sheet metal 
support. Maintain the 6” (152.4 mm) space.  There should 
also be a support sized to fit and hold the metal chimney 
connector. See that the supports are fastened securely to 
wall surfaces on all sides.  Make sure fasteners used to 
secure the metal chimney connector do not penetrate 
chimney flue liner.   
Method D.  2” (50.8 mm) Clearance to Combustible Wall 
Member:  Start with a solid-pak listed factory built chimney 
section at least 12” (304 mm) long, with insulation of 1” (25.4 
mm) or more, and an inside diameter of 8” (2 inches [51 mm] 
larger than the 6” [152.4 mm] chimney connector). Use this 
as a pass-through for a minimum 24-gage single wall steel 
chimney connector. Keep solid-pak section concentric with 
and spaced 1” (25.4 mm) off the chimney connector by way 
of sheet metal support plates at both ends of chimney 
section.  Cover opening with and support chimney section on 
both sides with 24 gage minimum sheet metal supports. See 
that the supports are fastened securely to wall surfaces on all 
sides. Make sure fasteners used to secure chimney flue liner.