119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
TANDBERG
Telepresence T3
POWER OUTlET fUSE 
REQUIREMENTS
The following minimum power outlet fuse requirements apply to the TANDBERG 
Telepresence T3:
ITEM
WATT
PlACEMENT
fUSE
ON/Off SWITCH
T1 Module × 3
2400
Back wall
A
1
Presentation 
splitter × 2 
60
Back wall
A
1
Table power outlet × 6
2400
Back wall
B
2
TCU
400
Back wall
C
2
Table quick buttons 
50
Back wall
C
2
Presentation input 
switch
5
Back wall
C
2
Touch collaboration 
display splitter
20
Back wall
C
2
Touch collaboration 
display
750
Back wall
C
2
Document camera
300
Ceiling
D
2
T3 Ceiling mounted 
lights
750
Ceiling
D
3
T3 LED Module
1000
Back- / Front wall
D
4
Total power
9335
Note!
 The table lists minimum fuse 
requirements. All electrical work must 
be done by electricians with local 
knowledge.
Note!
 Outside the room—adjacent to the 
entrance—there shall be an emergency 
power switch to switch off the power to 
the entire system and the room.
On the inside adjacent to the exit there 
shall be a sign with the following text:
fire emergency switch is 
located on the outside of 
this room.