Charles Bentley & Son AA Series Fascicule

Page de 2
Ordering Information
Optional Accessories
•  Remote summary relay
• Battery 
temperature
compensation
•  Low DC voltage alarm relay
•  High DC voltage alarm relay
•  Current failure relay
•  Combined Low/High voltage
alarm relays
•  AC power failure relay
Specifications
AC Input
108-132 volts/60 Hz (220 volts/50 Hz optional)
Operating Temperature
0º to 50º C (32º to 122º F)
Storage Temperature
-20º to 60º C (-4º to 140º F)
Cooling
Convection
DC Output
Float
2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium
Equalize
2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium
Current Limit
Approximately 135%
Enclosure
304 stainless steel hinged cover to facilitate installation
12 Volt
Model
Number
Height
Inches
Width
Inches
Depth
Inches
Approx.
Weight
D.C. Output
Amps
System
Voltage
24 Volt
32 Volt
AA1206*
6
12
11
9
8.5
12
AA1210*
10
12
11
9
8.5
14
AA1220*
20
12
11
9
8.5
22
AA2406*
6
24
11
9
8.5
14
AA2410*
10
24
11
9
8.5
22
AA2420*
20
24
13
16.5
8.5
38
AA3206
6
32
11
9
8.5
22
AA3210
10
32
11
9
8.5
26
0
10
20 30
40
50
60
70
80
90 100
% OF RATED CHARGING CURRENT (AMPS)
VPC
2.5
2.4
2.3
2.2
2.1
2.0
1.9
1.8
Equalize
Float
Typical Output Curve
*UL Listed
Contact your Charles sales representative for specific
product information.
When ordering, please specify:
1. Model number 
2. AC input: voltage & frequency 
3. Battery type and number of cells 
4. Ampere-hour capacity of battery 
5. Recharge time desired 
6. Description of load
7. Options
Charles Industries, Ltd.
Industrial Group
5600 Apollo Drive
Rolling Meadows, IL 60008 USA
Voice:  (847) 806-6300  
Fax:   (847) 806-6352 
E-mail: mktserv@charlesindustries.com
D-IND001-B01 Rev. 
3
IS0 9000
REGISTERED 
QUALITY SYSTEM