VEHICLE DETECTOR LOOP BLANKING FOR 
SWING GATES
 
The inside loop for a swing gate installation must be located at least 
4 feet outside of the arc of the gate. If it is not, the vehicle detector 
may detect the gate as it moves over the loop and cause the gate to 
reopen. If the gate is large and a single leaf, the arc usually requires 
that the loop be a considerable distance from the closed gate position. 
This may not be an effective position for the loop. In this case, a 
“blanking” or “shadow” loop may be used. 
A shadow loop detector is connected to the shadow loop terminal 
(#9) and the “common” terminal (#16) of the RS4000 control panel.   
Now, when the gate is in the fully open or closed position the vehicle 
detector will prevent the gate from closing when a vehicle is over the 
shadow loop. When the gate is opening or closing, the loop input is 
disabled. 
 
ELECTRICAL POWER REQUIREMENTS
 
The RS4000 is a 115 Volt AC gate operator. The AWG wire size for 
the electrical service is dependant upon the distance from the 
operator to the service breaker panel. Refer to Table 1 to determine 
the correct wire size to use. A 15 Amp service is required for each 
operator unit. 
The Nominal Distance column of Table 1 is the maximum 
recommended distance from the service breaker panel to the operator 
for a given wire size and voltage. The values in the table are valid for 
one RS4000 only. The RS4000 will operate at a voltage as low as 
105 VAC as measured at the input terminals to the operator. This 
should be checked as part of the installation procedure.   
Class 2 low voltage wiring from external controls such as a key pad, 
card reader, telephone entry device, etc. must be brought to the 
RS4000 operator by a separate conduit  from the 115 VAC electrical 
hook up conduit. Low voltage control wires MUST NEVER be 
routed in the same conduit as the HIGH VOLTAGE power wires. 
 
SERVICE CONDUIT
 
For new installations the conduit for the High Voltage may be 
brought to a junction box near where the RS4000 operator will be 
located or it may be brought directly to the 2 x 4 handy box inside 
the operator. 
 
WIRE SIZE 
NOMINAL DISTANCE 
#14 
100 FT 
#12 
150 FT 
#10 
250 FT 
#8 
400 FT 
#6 
600 FT 
#4 
1000 FT 
#2 
1600 FT 
 
WARNING! 
AVOID ELECTROCUTION:  
DO NOT ROUTE LOW VOLTAGE WIRES 
IN SAME CONDUIT AS HIGH VOLTAGE 
WIRES. FOLLOW ALL LOCAL 
ELECTRICAL CODES OR THE 
NATIONAL ELECTRICAL CODE.  
B:
 PREPARING THE SITE 
Figure 8:  Service 
Conduits - Bi-Parting 
106509 
Table 1