Xiii. Service and Maintenance
nOTiCE
Warranty does not cover boiler damage or 
malfunction if the following steps are not 
performed at the intervals specified.
A.
 
Continuously:
1.  Keep the area around the boiler free from 
combustible materials, gasoline and other flammable 
vapors and liquids.
2.  Keep the area around the combustion air inlet 
terminal free from contaminates .
3.  Keep the boiler room ventilation openings open and 
unobstructed.
B.
 
Monthly Inspections:
1.  Inspect the vent piping and outside air intake piping 
to verify they are open, unobstructed and free from 
leakage or deterioration.  Call the service technician 
to make repairs if needed.
2.  Inspect the condensate drain system to verify it is 
leak tight, open and unobstructed.  Call the service 
technician if the condensate drain system requires 
maintenance.
3.  Inspect the water and gas lines to verify they are 
free from leaks.  Call the service technician to make 
repairs if required.
CaUTiOn
Water leaks can cause severe corrosion damage 
to the boiler or other system components.  
immediately repair any leaks found.
C. 
 Annual Inspections and Service:   In addition to 
the inspections listed above the following should be 
performed by a service technician once every year. 
1.  If equipped, test the low water cutoff by pressing 
the “Test” button located at its end.  The yellow 
light should come on and “E12” should flash on 
the display.  Push the reset button on the display to 
restore normal operation.  If the yellow light does 
not come on, determine why the low water cutoff is 
not working properly. 
2.  Follow the procedure for turning the boiler off 
found in the Alpine™ Series Lighting and Operating 
Instructions.
DangER
This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high 
pressure.  assure that all gas and electric power supplies are off and that the water temperature is cool 
before attempting any disassembly or service.  
Do not attempt any service work if gas is present in the air in the vicinity of the boiler.  never modify, 
remove or tamper with any control device.
WaRning
This boiler must only be serviced and repaired by skilled and experienced service technicians.
if any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this 
manual.
if any electrical wires are disconnected during service, clearly label the wires and assure that the wires 
are reconnected properly.
never jump out or bypass any safety or operating control or component of this boiler.
Read, understand and follow all the instructions and warnings contained in aLL of the component 
instruction manuals.  
assure that all safety and operating controls and components are operating properly before placing 
the boiler back in service.