Equipment
Fuel
Description
Control Cabinet
Gas, #2 Oil, Gas/#2 Oil NEMA 1A with hinged door.
Control Voltage Transformer
Gas, #2 Oil, Gas/#2 Oil Included when burner voltage is greater than 120/60/1.
Motor Starter
Gas, #2 Oil, Gas/#2 Oil Contactor with single phase motor, magnetic starter with overload protection with         
3-phase motor.
Fusing
Gas, #2 Oil, Gas/#2 Oil Control circuit only.
Ignition
Gas and Gas/#2 Oil
Gas/Electric pilot.
#2 Oil
Direct spark (4F-63 to 4F-450).                                                                         
Gas/Electric (4F-563 and larger). 
Signal Lights
Gas, #2 Oil, Gas/#2 Oil Power On, Fuel On, Call for Heat and Alarm
Air Flow Safety Switch
Gas
All models
#2 Oil and Gas/#2 Oil
Models 4F-675 and larger.  Exception on #2 oil models 4F-63 to 4F-450 with integral 
oil pump.
Gas Train
Gas and Gas/#2 Oil
UL gas train for minimum inlet pressure indicated on Burner Information table.
Shipped unassembled and consisting of the following:
  Manual shut-off valve.
  Gas pressure regulator.
  Manual leak test valve.
  Automatic gas valve:  Diaphragm type with On-Off sequence.  Motorized all
     others (Proof of closure on 4F-675 and larger).
  Safety gas valve:  Solenoid type.
  Metering valve:  4F-675 and larger.
  High and Low gas pressure switches:  4F-311 and larger.
Oil Pump
#2 Oil and Gas/#2 Oil
Integral with burner (4F-63 to 4F-450).                                                           
Separate oil pump set with motor and accessories mounted on boiler skid  (4F-563 
and larger).
Oil Pressure Gauge
#2 Oil and Gas/#2 Oil
All models.
Pilot Gas Controls
Gas, #2 Oil, Gas/#2 Oil All models with gas/electric pilot have manual pilot shut-off valve, high gas pressure
regulator and solenoid gas valve.
Fuel Changeover
Gas/#2 Oil
Manual switch.
SERIES 4FH-50
5/02